Specifications
Voltage Rating
500 VAC
440 VDC
Ampere Range
2-630 A
Interrupting Rating
120 kA AC
25 kA DC
Standards
DIN 43.620, IEC 269-2-1
Approvals VDE
Example part number NH1CG25 (size, characteristic and amperage)
Indication
All NH fuse links incorporate a
blown fuse indicator
Recommended Fuse Holders
NHB Series Fuse Base
NHF Series Disconnects
Ordering Information
AmperAge
gl-gg 500 V OrDeriNg Number
am 500 V OrDeriNg Number
NH00C / NH00
NH0
NH1C / NH1
NH2C / NH2
NH3C / NH3
NH00Cm
NH1
NH2
NH3
2
NH00CG2
—
—
—
—
NH00CM2
—
—
—
4
NH00CG4
—
—
—
—
NH00CM4
—
—
—
6
NH00CG6
NH0G6
—
—
—
NH00CM6
—
—
—
10
NH00CG10
NH0G10
—
—
—
NH00CM10
—
—
—
16
NH00CG16
NH0G16
—
—
—
NH00CM16
—
—
—
20
NH00CG20
NH0G20
—
—
—
NH00CM20
—
—
—
25
NH00CG25
NH0G25
NH1CG25
—
—
NH00CM25
—
—
—
32
NH00CG32
NH0G32
NH1CG32
—
—
NH00CM32
—
—
—
35
NH00CG35
NH0G35
NH1CG35
—
—
NH00CM35
—
—
—
40
NH00CG40
NH0G40
NH1CG40
NH2CG40
—
NH00CM40
—
—
—
50
NH00CG50
NH0G50
NH1CG50
NH2CG50
—
NH00CM50
—
—
—
63
NH00CG63
NH0G63
NH1CG63
NH2CG63
—
NH00CM63
NH1M63
—
—
80
NH00CG80
NH0G80
NH1CG80
NH2CG80
—
NH00CM80
NH1M80
—
—
100
NH00CG100
NH0G100
NH1CG100
NH2CG100
—
NH00CM100
NH1M100
—
—
125
NH00G125
NH0G125
NH1CG125
NH2CG125
—
—
NH1M125
NH2M125
—
160
NH00G160
NH0G160
NH1CG160
NH2CG160
—
—
NH1M160
NH2M160
—
200
—
—
NH1G200
NH2CG200
—
—
NH1M200
NH2M200
—
224
—
—
NH1G224
NH2CG224
—
—
NH1M224
NH2M224
—
250
—
—
NH1G250
NH2CG250
—
—
NH1M250
NH2M250
—
300
—
—
—
NH2G300
—
—
—
NH2M300
—
315
—
—
—
NH2G315
NH3CG315
—
—
NH2M315
NH3M315
355
—
—
—
NH2G355
NH3CG355
—
—
NH2M355
NH3M355
400
—
—
—
NH2G400
NH3CG400
—
—
NH2M400
NH3M400
425
—
—
—
—
NH3G425
—
—
—
—
500
—
—
—
—
NH3G500
—
—
—
NH3M500
630
—
—
—
—
NH3G630
—
—
—
NH3M630
Web Resources
For the latest international fuse products, visit:
Littelfuse.com/nh
Description
Littelfuse
®
European style NH fuse links are designed for the
protection of conductors and motors. The gL-gG characteristic
fuse links are generally used to protect cables and installation
lines from overloads and short-circuits. The aM characteristic
fuse links are used for the short-circuit protection of motors
and switchgear. They are available in NH00C to NH3 sizes
up to 630 A.