Description
The T2400 3-Phase Dual Overcurrent Relay includes two
combined overcurrent relays, designed for protection or
monitoring of generators and power transmissions. A typical
application is to use one of the overcurrent functions to trip the
generator circuit breaker, and the other overcurrent function to
trip a non-essential consumer.
The T2400 consists of two overcurrent circuits with similar
current settings and time delays. Each circuit detects the
highest of the 3 input currents and, if this exceeds the preset
level (0.5-1.4 x I
N
), the corresponding pick-up LED will indicate
and the delay timer will be started. After the preset time
(3-30 sec.) has expired, the corresponding output relay and
LED will be activated, provided that the current level was
exceeded for the entire delay time.
Specifications
Trip Level
0.5-1.4 x I
N
Delay
3-30 sec.
Max. Voltage
660 V
Voltage Range
60-110%
Consumption
Voltage 5 VA at U
N
Current 0.3 VA at I
N
Continuous Current
2 x I
N
Frequency Range
45-400 Hz
Output Relay
Normally de-energized
Contact Rating
AC: 400 V, 5 A, 2000 VA; DC: 150 V, 5 A, 150 W
Overall Accuracy
±5%
Repeatability
±1%
Operating Temperature –20°C to + 70°C
Dielectric Test
2500 V, 50 Hz
EMC
CE according to EN50081-1, EN50082-1,
EN50081-2, EN50082-2
Approvals
Certified by major marine classification societies
Burn-in
50 hours before final test
Enclosure Material
Polycarbonate. Flame retardant
Weight
0.5 kg
Dimensions H
70 mm (2.76”); W 100 mm (3.94”);
D 115 mm (4.52”)
Installation
35 mm DIN rail or 4 mm (
3
/
16
”) screws
OrderinG
number
TerminalS
i
n
FuncTiOn
1-3
2-3
T2400.0010 230 V
5 A
T2400.0020 450 V
400 V 5 A
T2400.0030 110 V
100 V 5 A
T2400.0040 450 V
400 V 5 A Latching output on relay 1,
6-60 sec. delay on relay 1
T2400.0050 480 V
415 V 5 A
T2400.0060 450 V
400 V 1 A
T2400.0070 450 V
400 V 5 A Latching output on relay 1,
normally energized relay 1
T2400.0080 127 V
120 V 5 A
T2400.0090 24 Vdc
5 A
Ordering Information
Simplified Circuit Diagram
Features & Benefits
Latching output relays are reset by disconnecting the power supply.
Other supply voltages and combinations are available on request.
I. OVERCURRENT
II. OVERCURRENT
I
1
U
I
2
I
3
2
11
12
13
14
15
16
1
3
10
9
8
7
6
5
4
L
1
L
2
L
3
SUPPLY
T2400
(3-Phase Dual
Overcurrent Relay)
FeaTureS
beneFiTS
Accepts high supply
voltage variation
Ensures correct operation in spite of voltage
supply fluctuations (fulfills marine class
requirement)
Visual indication of
power, pick-up, and
output trip
Provides quick and concise status information
Direct line-line or line-
neutral voltage supply
(up to 690 Vac)
Simplifies design and installation.
No need for PTs.
Combining 2 relays in
same enclosure
Economic solution for non-essential load
tripping, and occupying less space in the
switch panel
Galvanic isolated inputs
Protects the unit against high AC voltage and
currents from the installation including spikes
DIN-rail or screw-mount
& adjustment by
potentiometers
Easy installation
Rev: 4-A-050213