Generator & Single-Function Protection–Overcurrent/Short-Circuit
T2500 SerieS
Overcurrent and Short-Circuit Relay
Description
The combined T2500 3-Phase Overcurrent and Short-Circuit
Relay is used for protection of generators and power
transmissions. The short-circuit relay protects against faults
causing high currents, and the overcurrent relay protects
against thermal damage.
Specifications
Overcurrent Trip Level 0.5-1.4 x I
N
Delay
3-30 sec.
Short-Circuit Trip Level 1.0-4.0 x I
N
Delay
0.1-1.0 sec.
Max. Voltage
660 V
Voltage Range
60-110%
Consumption
5 VA at U
N
Continuous Current
2 x I
N
Frequency Range
45-400 Hz
Output Relay
Normally energized
Extra Output Relay
Normally de-energized
Contact Rating
AC: 400 V, 5 A, 2000 VA; DC: 150 V, 5 A, 150 W
Overall Accuracy
±5%
Repeatability
±1%
Operating Temperature –20°C to + 70°C
EMC
CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Approvals
Certified by major marine classification societies
Burn-in
50 hours before final test
Enclosure Material
Polycarbonate. Flame retardant
Weight
0.5 kg
Dimensions H
70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”)
Installation
35 mm DIN rail or 4 mm (
3
/
16
”) screws
OrderinG
number
TerminalS
i
n
FunCTiOn
1-3
2-3
T2500.0010 450 V 400 V 5 A
Latching output, resetable
T2500.0020 230 V
5 A
Latching output, resetable
T2500.0030 480 V 415 V 5 A
Latching output, resetable
T2500.0040 450 V 400 V 1 A
Latching output, resetable
T2500.0050 24 Vdc
5 A
Latching output, resetable
T2500.0060 230 V
5 A
De-energized extra output relay
T2500.0070 450 V 400 V 5 A
De-energized extra output relay
T2500.0080 450 V 400 V 5 A
De-energized extra output relay,
latching outputs
T2500.0090 480 V 415 V 5 A
De-energized extra output relay
T2500.0100 24 Vdc
1 A
De-energized extra output relay
T2500.0110 450 V 400 V 5 A
De-energized extra output relay,
latching short circuit output
T2500.0120 24 Vdc
5 A
De-energized extra output relay,
de-energized relay 1, no internal
power backup
Ordering Information
Simplified Circuit Diagram
Other combinations and voltages are available on request.
Features & Benefits
SUPPLY
SHORT CIRCUIT
OVERCURRENT
I
1
U
I
2
I
3
19
17
18
20
2
3
11
12
13
14
15
16
1
10
9
8
7
6
5
4
L
1
L
2
L
3
T2500
(Overcurrent & Short-Circuit Relay)
FeaTureS
beneFiTS
Accepts high supply
voltage variation
Ensures correct operation in spite of voltage
supply fluctuations (fulfills marine class
requirement)
Visual indication of
power, pick-up, and
output trip
Provides quick and concise status information
Direct line-line or line-
neutral voltage supply
(up to 690 Vac)
Simplifies design and installation.
No need for PTs.
Combining 2 protection
functions in same
enclosure
Economic solution, occupying less space in
the switch panel
Available with extra
output
Economic solution for non-essential load
tripping
Versions available with
separate 24 Vdc supply
Safe operation–Maintains protection
regardless of system voltage failure
Galvanic isolated inputs
Protects the unit against high AC voltage and
currents from the installation including spikes
DIN-rail or screw-mount
& adjustment by
potentiometers
Easy installation
Connection between 20 and 19 gives instant operation of Relay 2.
Connection between 20 and 17 gives delayed operation of Relay 2.
Connection between 20 and 18 gives synchronized operation of Relay 1 and Relay 2.
Disconnecting the diode between 17 and 18 will disable operation of Relay 1 from
overcurrent.
Latching output relays can be reset or disabled by bridging terminals 5 and 6.
Rev: 4-A-050213