Littelfuse T2000 Series User Manual
T2000 series, Protection relays & controls, Reverse power relay description

Protection Relays & Controls
© 2013 Littelfuse Protection Relays & Controls
9
5
C/B TRIP
10
6
L - L SUPPLY
7
8
1
3
2
RESET
13
14
LOAD
1
2
3
L
L
L
T2000
(Reverse
Power
Relay)
G
Littelfuse.com/t2000
Generator & Single-Function Protection–Reverse Power
T2000 SeRieS
Reverse Power Relay
Description
Under parallel operation, the T2000 Reverse Power Relay will
protect the generator from being run as an electric motor. The
T2000 will protect the prime mover of the generator against
physical damage, but will also protect the parallel running
generators from overload caused by the inversed load shift in
a reverse power situation.
The T2000 calculates I x cos F, representing the active
power. If the active power becomes negative and exceeds
the preset level (2-20%), the pick-up LED will indicate
this and the delay timer will be started. After the preset
time (2-20 sec.) has expired, the output relay and LED will
be activated, provided that the reverse power level was
exceeded for the entire delay time.
Specifications
Trip Level
2-20% I
N
Delay
2-20 sec.
Max. Voltage
660 V
Voltage Range
50-110%
Consumption
5 VA at U
N
Continuous Current
2 x I
N
Frequency Range
45-400 Hz
Output Relay
Normally de-energized, latching, resetable
Contact Rating
AC: 400 V, 5 A, 1250 VA
DC: 150 V, 5 A, 120 W
Overall Accuracy
±5%
Repeatability
±1%
Operating Temperature –20°C to + 70°C
EMC
CE according to EN50081-1, EN50082-1,
EN50081-2, EN50082-2
Approvals
Certified by major marine classification societies
Burn-in
50 hours before final test
Enclosure Material
Polycarbonate. Flame retardant
Weight
0.5 kg
Dimensions H
70 mm (2.76”); W 100 mm (3.94”);
D 115 mm (4.52”)
Installation
35 mm DIN rail or 4 mm (
3
/
16
”) screws
ORdeRinG
numbeR
TeRminalS
i
n
SuPPly FuncTiOn
1-3
2-3
T2000.0010
230 V
5 A L-N
T2000.0020
450 V 400 V 5 A L-L
T2000.0030
127 V 120 V 5 A L-N
T2000.0040
110 V 100 V 5 A L-L
T2000.0050
110 V 100 V 5 A L-L
No time delay
T2000.0060
230 V
1 A L-N
T2000.0070
660 V
5 A L-L
T2000.0080
450 V 400 V 5 A L-N
Delay 0.2 - 2.0 sec.
T2000.0090
127 V 120 V 5 A L-L
T2000.0100
110 V 100 V 1 A L-L
T2000.0110
450 V 400 V 5 A L-L
No time delay
T2000.0120
480 V 415 V 5 A L-L
T2000.0130
230 V
5 A L-N
No time delay
T2000.0140
230 V
5 A L-L
T2000.0150
480 V 415 V 1 A L-L
T2000.0160
450 V 400 V 1 A L-L
Ordering Information
Simplified Circuit Diagram
Other supply voltages and combinations are available on request.
FeaTuReS
beneFiTS
Accepts high supply
voltage variation
Ensures correct operation in spite of voltage
supply fluctuations (fulfills marine class
requirement)
Visual indication of
power, pick-up, and
output trip
Provides quick and concise status information
Direct line-line or line-
neutral voltage supply
(up to 690 Vac)
Simplifies design and installation. No need for
PTs or separate power supply
Available with instant
output trip
Enables alternative use for detection of current
direction
Galvanic isolated inputs
Protects the unit against high AC voltage and
currents from the installation including spikes
DIN-rail or screw-mount
& adjustment by
potentiometers
Easy installation
Features & Benefits
Rev: 4-A-050213