Littelfuse PGR-3200 Series User Manual
Pgr-3200 series, Protection relays & controls, Ground-fault protection – ungrounded ac system
Protection Relays & Controls
© 2013 Littelfuse Protection Relays & Controls
Littelfuse.com/pgr-3200
Ground-Fault Protection – Ungrounded AC System
A
PGR-3100
UNGROUNDED
SUPPLY
B
C
A
L2
PGR-3200
L1
B
C
(Ground-Fault
Indication System)
(Ground-Fault
Protection System)
PGR-3200 SeRieS
Ground-Fault Protection System
Description
The PGR-3200 detects ground faults by continuously
monitoring the insulation integrity of ungrounded electrical
systems. The relay monitors the insulation for damage and
assists with predictive maintenance and troubleshooting of
developing ground faults by providing two warning and an
alarm level. The PGR-3200 operates on one- or three-phase
ungrounded systems up to 6 kV.
The PGR-3200 can also be used on a grounded system to
monitor the insulation for damage, while the power system
is de-energized. The mode-of-operation terminals (27-28)
are connected to the circuit breaker or contactor auxiliary
contacts to toggle the relay off when the contactor or breaker
is closed.
Specifications
IEEE Device Numbers
Undervoltage Relay (27)
Ground Detector Relay (64)
Input Voltage
See ordering information
Dimensions
H 75 mm (3”); W 100 mm (3.9”); D 110 mm (4.3”)
Resistance Ratings
Insulation warning (30 kΩ
and 50 kΩ
)
Insulation alarm
(10 kΩ
)
Contact Operating Mode Non-fail-safe
Test Button Local
Reset Button
Local and remote
Output Contacts
Two Form C
Analog Output
0-1 mA
Conformally Coated
Consult factory
Warranty
5 years
Mounting
DIN, Surface
ORdeRinG nUmbeR
COntROl POweR
PGR-3200
240 Vac
PGR-3200-120
120 Vac
Ordering Information
Simplified Circuit Diagram
Note: For optional conformal coating please consult factory. To convert to a resistance
grounded system, see neutral-grounding-resistors packages.
PGH Series High-Tension Coupler
A PGH Series high-tension coupler is required
for systems between 1,300 V and 6,000 V.
PGA-0510 Analog Ohm Meter
Optional PGA-0510 Analog Meter allows
for metering of insulation resistance.
FeAtUReS
beneFitS
NEC
®
and CEC Code
compliant
Meets National Electrical Code (NEC
®
) Article
250.21(B) and Canadian Electrical Code Part 1,
Section 10-106 (2) requirements for ungrounded
systems
Output contact
(50 k
Ω
)
Form C output contact for alarming when the
insulation resistance is below 50 k
Ω
Output contact
(10 k
Ω
)
Form C output contact for tripping when the
insulation resistance is below 10 k
Ω
Analog output
(0 - 1 mA)
Provides means for connecting to an optional
meter (PGA-0510) or control system
DIN-rail or surface
mount
Flexible options for ease of installation
Features & Benefits
Accessories
A
A
ACCeSSORieS
ReqUiRement
PGH Series
Required >1,300 V
PGA-0510
Optional
Rev: 4-A-050213
Based on Manual Rev 3a