Technical specifications, Ppi-600v parallel path isolator, Isclaimer – Littelfuse PPI-600V User Manual
Page 2
![background image](/manuals/292141/2/background.png)
PPI-600V Parallel Path Isolator
Rev. 0
Oct. 13, 2011 PPI-600V Parallel Path Isolator Datasheet
TYPICAL APPLICATION
GROUND CHECK MONITOR
SE134C, SE-135, SE-105 OR SE-125
CABLE
GROUND
G
CABLE
GROUND
GC
INCOMING
GROUND CHECK
INCOMING
GROUND
GC
G
INCOMING
GROUND-CHECK
TERMINATION
CHASSIS GROUND BUS
PPI-600V
GC
G
OUTGOING
GROUND CHECK
OUTGOING
GROUND
OUTGOING
GROUND CHECK
TERMINATION
NOTES:
1. PARALLEL PATH ISOLATOR IS NOT POLARIZED.
EITHER FLANGE CAN BE CONNECTED TO CHASSIS.
2. THE OUTGOING GROUND MUST BE ISOLATED FROM THE
CHASSIS GROUND BUS. IF A FLANGE-MOUNTED RECEPTACLE
IS USED, VERIFY THAT THE FLANGE IS ISOLATED FROM THE
GROUND PIN, AND
- USE A MATING PLUG WITH A NON-METALLIC HOUSING, OR
- ISOLATE THE FLANGE FROM THE CHASSIS IF THE MATING
PLUG HAS A METALLIC HOUSING.
3. CABLE PLUGS AND RECEPTACLES WITH GROUNDED METAL
HOUSINGS MUST BE ISOLATED FROM EARTH TO PREVENT
PARALLEL GROUND PATHS.
4. FOR SYSTEMS ABOVE 600 VAC, CONNECT A V131DA40 MOV ACROSS
THE PPI-600V.
TECHNICAL SPECIFICATIONS
Dimensions:
Height ......................................... 102 mm (4.0”)
Width .......................................... 235 mm (9.3”)
Depth .......................................... 64 mm (2.5”)
Shipping Weight ........................ 11.5 lb (5.5 kg)
Off-State Resistance .................. >20 kΩ @ 125°C
and V < 10.0 V
On-State Voltage ....................... < 2 V @ 25°C
and
I<2000
A
Minimum Trigger Voltage ........ 20 V
Maximum Trigger Voltage ....... 25 V
Clamp Rating:
1 Cycle .................................. 15 kA
10
second
.............................. 2.5 kA
Failure Mode .............................. Short Circuit
D
ISCLAIMER
Specifications are subject to change without notice.
Littelfuse Startco is not liable for contingent or
consequential damages, or for expenses sustained as a result
of incorrect application, incorrect adjustment, or a
malfunction.