Littelfuse JLS Series User Manual
Class j – jls series fuses, Powr-gard, Fuse datasheet
© 2012 Littelfuse POWR-GARD
®
Products
www.littelfuse.com
Rev: 100112
1 of 2
POWR-GARD
®
Fuse Datasheet
CLass J – JLs series FUses
600 VAC • Fast-Acting • 1-600 A
ampere ratings
1
20
45
90
175
350
3
25
50
100
200
400
6
30
60
110
225
450
10
35
70
125
250
500
15
40
80
150
300
600
Description
JLS series fuses provide space saving, fast-acting overload
and short-circuit protection for non-inductive loads.
For ap pli ca tions where short-duration surg es and spikes may
cause nuisance fuse opening, consider the use of Littelfuse
POWR-PRO
®
JTD or JTD_ID series time-delay fuses.
Applications
• General purpose circuits with little or no motor load.
• Resistive loads, such as resistance electric heat.
• Loads requiring fast-acting overload protection, such as
equipment containing solid-state devices.
Specifications
Voltage Ratings
600 VAC
Interrupting Ratings
200 kA rms symmetrical
Ampere Range
1–600 A
Approvals
Standard 248-8, Class J
UL Listed (File: E81895)
CSA Certified (File: LR29862)
Federal Specification WF-1814
(QPL-W-F-1814)
10000
100000
200000
100
1000
100
1000
10000
100000
1000000
600 A
400 A
200 A
100 A
60 A
30 A
PEAK LET
-THRU IN AMPERES
AVAILABLE FAULT CURRENT
SYMMETRICAL R. M. S. AMPERES
05567005
type
series amperage
CataLog
nUmber
ordering
nUmber
nOn-inDiCAtinG
JLS
110
JLS110
0JLS110.X
Ordering Information
Dimensions
Please refer to the Class J dimensions on page 2
Web Resources
TC curves, downloadable CAD drawings and other technical
information: Littelfuse.com/jls
Recommended Fuse Holders
LFJ60 Series
(cover is not compatible with JLS series fuses)
LFPSJ Series (
8
⁄
10
–60 A)
Peak Let-Thru Curve
QPL
JLS