Spxi series in-line solar fuse, Powr-gard, Fuse datasheet – Littelfuse SPXI Series User Manual
Page 2: Electrical specification – agency requirements, Temperature rerating curve, Ordering information, Electrical specifications, Temperature of air immediately surrounding fuse)
![background image](/manuals/292003/2/background.png)
littelfuse.com
© 2014 Littelfuse POWR-GARD
®
Products
Rev: 020414
POWR-GARD
®
Fuse Datasheet
2 of 3
Electrical Specification – Agency Requirements
amPerage ratIng
oPenIng tIme (mInUteS)
135% of amp rating per UL
200% of amp rating per UL
2.5-3.5
60 Max
4 Max
SPXI SerIeS In-LIne SoLar FUSe
PERCENT OF UPRA
TING
PERCENT OF DOWNRA
TING
AMBIENT TEMPERATURE
60
40
20
0
0
20
40
60
-60˚ C -40˚ C
-20˚ C
0˚ C
20˚ C
40˚ C
60˚ C
80˚ C
100˚ C
120˚ C
140˚ C
-76˚ F -40˚ F
-4˚ F
-32˚ F
68˚ F
104˚ F
140˚ F
176˚ F
212˚ F
248˚ F
284˚ F
Temperature Rerating Curve
(Temperature of Air Immediately Surrounding Fuse)
Ordering Information
SerIeS
amPerage amP code
cataLog nUmber
ProdUct markIng
Pack QUantIty
orderIng nUmber
UPc
SPXI
2.5
02.5
SPXI02.5
SPXI 2 1/2
10
SPXI02.5T
07945880950
50
SPXI02.5L
07945880949
SPXI
3.5
03.5
SPXI03.5
SPXI 3 1/2
10
SPXI03.5T
07945880808
50
SPXI03.5L
07945880149
Electrical Specifications
am
Perage
VoLtage InterrUPtIng
ratIng
WIre range
nom coLd
reSIStance
(ohm)
WattS LoSS
at 100% rated
cUrrent (W)
WattS LoSS
at 80% rated
cUrrent (W)
WattS LoSS
at 70% rated
cUrrent (W)
meLtIng
I
2
t (a
2
s) 15 ka
(1500Vdc)
totaL
cLearIng
I
2
t (a
2
s) 15 ka
(1500Vdc)
agency
aPProVaLS
dc
ac
dc
UL recognIzed
2.5
1500
–
15 kA 10 AWG (6 mm
2
)
0.099
0.859
0.482
0.350
6.78
15.78
•
3.5
1500
–
15 kA 10 AWG (6 mm
2
)
0.0711
1.56
0.81
0.57
25
50
•