Description
The G2000 Power Relay is intended for detection of power
level for protection, control and monitoring purposes. In
the default configuration, the G2000 acts as a reverse
power relay for protection of generators running in parallel.
Basic adjustments can be done on the dials on the front
panel. More configuration options are available through PC
configuration via the optional G0100 Programming Kit. PC
programming enables the user to reconfigure the relay as an
overload relay and allows extension of the ranges on the dials
on the front panel.
One version covers all system voltages from 63 Vac to
690 Vac. Rated voltage can be adjusted by a preset button or
PC configuration. Auxiliary supply voltage is 24 Vdc.
Specifications
Supply
8-36 Vdc/0.75 W at 24 Vdc
Input Voltage
63-690 Vac ± 30%
Input Current
5 A CT, max. 10 A
Frequency
35-75Hz
Trip Level
RP: 2-20% (max. 2-50%)
FP: 50-140% (max. 50-150%)
Hysteresis
1-10% (max. 1-50%)
Delay
2-20 sec. (max. 1-360 sec.)
Relay Rating
380 Vac, 5 A, 1250 VA, 150 Vdc, 5 A, 120 W
Pick-up Relay
Normal state: ND (NE)
Latching: Non-latching
Trip Relay
Normal state: ND (NE)
Latching:
Non-latching (latching)
Reset
Automatic (manually by terminal 11)
Accuracy
± 5%
Repeatability
± 1%
Serial Link RJ11-modular
Operating Temperature
–20°C to + 70°C
EMC EN50263
Burn-in
50 hours before final test
Enclosure Material
Polycarbonate. Flame retardant
Weight
0.3 kg
Dimensions
H 73 mm (2.87”); W 75 mm (2.95”);
D 114 mm (4.49”)
Installation
35 DIN rail or two 4 mm, (
3
/
16
”) screws
OrderinG number
COntrOl POwer
G2000.0010
24 Vdc, 5 A
Ordering Information
Simplified Circuit Diagram
G0100 Programming Kit
Connects to RS232 port. Includes blank front-
plate labels and permanent pen for texting scales.
FeatureS
beneFitS
PC configuration
Forward power or reverse power
relay functionality
User configurable scales and
setpoints
Suits broad variety of applications
63 Vac to 690 Vac systems can
be monitored by the same unit
Supports wide range of system voltages
Features & Benefits
Accessories
aCCeSSOrieS
requirement
G0100
Optional
Rev: 4-A-050213