Littelfuse LFCL Series User Manual
Cable limiters, Powr-gard, Fuse datasheet

POWR-GARD
®
Fuse Datasheet
© 2013 Littelfuse POWR-GARD
®
Products
Littelfuse.com
Rev: 012313
1 of 1
Cable limiters
600 VAC
LFCL - 500 - C - 1
Terminal Material
Littelfuse
Cable Limiter
Type of
Termination
Conductor Size
(Aluminum or Copper)
DesCription
Catalog number
type termination Cable size
Cable type
Cop per
aluminum
1
CAbLe tO CAbLe
4/0
LFCL4/0C1
LFCL4/0A1
250MCM
LFCL250C1
LFCL250A1
350MCM
LFCL350C1
LFCL350A1
500MCM
LFCL500C1
LFCL500A1
750MCM
LFCL750C1
LFCL750A1
3
CAbLe tO
OFFset bus
4/0
LFCL4/0C3
LFCL4/0A3
250MCM
LFCL250C3
LFCL250A3
350MCM
LFCL350C3
LFCL350A3
500MCM
LFCL500C3
LFCL500A3
750MCM
LFCL750C3
LFCL750A3
5
stRAiGht bus
tO OFFset bus
4/0
LFCL4/0C5
—
250MCM
LFCL250C5
—
350MCM
LFCL350C5
—
500MCM
LFCL500C5
—
750MCM
LFCL750C5
—
6
MOLe tO CAbLe
4/0
LFCL4/0C6
LFCL4/0A6
250MCM
LFCL250C6
LFCL250A6
350MCM
LFCL350C6
LFCL350A6
500MCM
LFCL500C6
LFCL500A6
750MCM
LFCL750C6
LFCL750A6
8
MOLe tO
OFFset bus
4/0
LFCL4/0C8
—
250MCM
LFCL250C8
—
350MCM
LFCL350C8
—
500MCM
LFCL500C8
—
750MCM
LFCL750C8
—
Note: For Type 5 and Type 8 Aluminum cable limiters, use the Copper Type C5 and C8.
Description
Cable limiters are fusible devices that provide very fast
short-circuit protection, primarily to faulted cables, but also to
other conductors such as busway. Cable limiters do not have
an ampere rating, and cannot be used to provide overload
protection. They are instead selected by cable size; for example,
a 500 kcmil cable requires a 500 kcmil cable limiter. Their
main use is to isolate faulted cables in circuits con tain ing
three or more parallel conductors per phase. They may be
installed on the line side of the main service to provide short-
circuit protection to the service conductors. This is especially
important when service conductors are tapped from large low
voltage networks or from large low impedance transformers.
Cable limiters have terminals which permit them to be installed
in a variety of equipment. The most common configuration is
the offset blade on one end and the crimp terminal on the other
end. This permits the limiter to replace a cable terminal (lug).
Applications
• Service entrance conductors
• Between transformer or network bus and busway
terminal boxes
• Large feeders with three or more conductors per phase
Features
• Current-limiting characteristics provide pro tec tion to
conductor insulation and reduce damage when faults occur.
• Properly applied cable limiters may permit the use of
equip ment with reduced withstand ratings
• Wide variety of terminations and cable ratings permit use
in almost every situation.
Specifications
Voltage Ratings
600 VAC
Interrupting Rating
200 kA
Cable Size Range
4/0 – 75MCM Copper or Aluminum
Note: For Type 5 and Type 8 Aluminum cable limiters, use the Copper Type C5 and C8.
Ordering Information
Web Resources
For additional information, see website:
www.littelfuse.com/lfcl