Littelfuse LDC Series User Manual
Class l – ldc series fuses, Powr-gard, Fuse datasheet
POWR-GARD
®
Fuse Datasheet
© 2012 Littelfuse POWR-GARD
®
Products
www.littelfuse.com
Rev: 100112
1 of 2
Class l – lDC series FUses
600 V AC/DC • Time-Delay • 150-2000 A
Description
High DC voltage and interrupting ratings make the
POWR-PRO
®
LDC ideal for DC applications. The DC
interrupting performance exceeds UL listing requirements.
Applications
• Solar inverter and array protection
• UPS protection especially for large battery circuits
• DC distribution and variable speed drives
• Mass transit systems
Features/Benefits
• POWR-PRO
®
Performance
• Extremely Current-Limiting
• 600 V AC/DC rated
• 200 kA AC Interrupting Rating
• 50 kA DC Interrupting Rating
Specifications
Voltage Ratings
AC: 600 V
DC: 600 V
Interrupting Ratings
AC: 200 kA rms symmetrical
DC: 50 kA (16 millisecond time-constant)
Ampere Range
150–2000 A
Approvals
Standard 248-10, Class L
UL Listed 601–2000 A (File: E81895)
UL Recognized 150–600 A
(File: E71611)
CSA Certified 150–2000 A
(File: LR29862)
ampere ratings
150
450
750
1201
1601
200
500
800
1300
1800
250
600
900
1350
1900
300
601
1000
1400
2000
350
650
1100
1500
400
700
1200
1600
Web Resources
TC Curves, downloadable CAD drawings and other technical
information: www.littelfuse.com/ldc
Dimensions
Please refer to the Class L dimensions page 2
Peak Let-Thru Curve
Note: For more information, see Peak Let-Thru Table
series
amperage
Catalog nUmber orDering nUmber
LDC
700
LDC700
0LDC700.X
Ordering Information
LDC