beautypg.com

Littelfuse T4000 Series User Manual

T4000 auto synchronizer, Application, Function

background image

T4000 Auto Synchronizer

• Automatic synchronization with

voltage based speed control

• Adjustable stability and phase angle.

• Visual indication of bus voltage,

generator voltage and closing signal

• Output adaptable to most electronic

speed controllers

• Automatic or remote reset of output

• Cost effective and highly reliable

compact design

• 50 hours burn-in before final test

• Operating temperature range:

-20°C to +70°C

• Certified by major marine

classification societies

• Flame retardant enclosure

• Screw or DIN rail mounting

Application

The T4000 Auto Synchronizer provides

automatic synchronization of an

incoming generator to a busbar in a

minimum of time.

The T4000 operates in connection with

most electronic speed controllers. Via the

speed controller the T4000 controls the
speed and phase of the generator in order

to match it to the busbar. The T4000 will

lock the phase and frequency once accor-

dance is obtained, thus enabling the

generator to stay in synchronisation with

the bus bar without closing the breaker.

Together with the T4400 Load Sharer,

the T4000 provides the optimal solution

for generator control, both in marine

and land-based applications. The T4000

is type approved by major marine

classification societies.

Function

The T4000 measures the voltage across

two phases on either side of the circuit

breaker in order to obtain data on frequency,

phase and voltage difference for closing

the circuit breaker at phase accordance.

The limits for the closing signal are

adjustable on the dial PHASE ANGLE.

The phase can be adjusted between ±6°

and ±9°, and voltage difference between

±10 % and ±15%. When the difference

in voltage, phase and frequency are

within limit for 0.5 seconds, a closing

signal to the circuit breaker is generated,

provided that CLOSE ENABLE is activa-

ted (terminals 12 and 13 interconnected).

The relay LED indicates when within

limits and a jumper between terminals

12 and 13 (CLOSE ENABLE) will enable

the closing contact CLOSE (terminals 9

and 10). The closing signal is maintained

for a minimum duration of 0.5 seconds.

When commissioning, it is recommended to

disconnect the closing signal by opening

the jumper between terminals 12 and 13.

Check that the closing signal indicated on

the relay LED is at phase accordance.

The DC control signal to the speed

controller must be reset when the circuit

breaker is closed. A jumper between

terminals 12 and 15 (AUTO RESET)

gives delayed automatic reset.

Alternatively a normally closed auxiliary

circuit breaker contact, connected to

terminals 12 and 14 (OPEN TO RESET),

gives remote reset when the contact is

opened. Reset is also obtained if the bus

or generator voltage drops below

approximately 50% of nominal voltage.

Impedance adaption of the output

(OUTPUT TO GOV.) to individual

electronic speed controllers can be done

using terminals 23 to 26. Output on

terminal 22 is variable (adjustable by a

screwdriver at VARIABLE OUT 22).

Alternatively, other impedance values can

be obtained by connecting an external

resistor between terminals 21 and 27.

The resistance is selected so that a speed

deviation range of ±3 Hz is possible.

The stability is adjusted on the dial

STABILITY for the fastest phase accor-

dance which does not cause overshoot.

Fig. 1. Application Diagram.

GEN.

24

8

OUTPUT TO GOV.

AUTO-SYNCHRONIZER

BUS.

GEN.

C/B

1

BUS

3

L

2

L

1

L

2

3

SYNC.

ON

4

5

7

6

ANGLE

PHASE

17

18

19

FORV.

INV.

BUS.

23

20

21

22

COMM.

CONT.

GEN.

STABILITY

CLOSE ENABLE

Application diagram

C/B NC

9

10

11

12

15

14

13

16

AUTO RESET
OPEN TO RESET

25

28

26

27

T4000

CLOSE

NC.

32

29

30

31

OUT. 22

VARIABLE

RELAY

ELECTRONIC GOVERNOR

GAS ENGINE

AUTO-SYNCHRONIZER

T4000