APPLYING POWER (702M12-W)


The M12 A coded power connector is keyed, where the mating connection from the power supply
can be made only when the male and female ends are lined up properly.

Verify the Power LED stays ON (GREEN).

Notes:

• Only 1 power supply must be connected to power for minimal operation. For redundant power

operation, V

1

and V

2

inputs must be connected to separate DC Voltage sources. This device will

draw current from both sources simultaneously. Use 16-28 gauge wire when connecting to the
power supply.

• The LAN port supports Power over Ethernet and can be used redundantly with the power input

mentioned above.



Recommended 24V DC Power Supplies, similar to: N-Tron’s P/N NTPS-24-1.3: (NOTE: Not appropriate
for use with M12, POE, and HV models.)

• Input AC 115/230V

• Output DC 24-28V

• Output Current 1.3A @ 24V
1.0A @ 28V

• Power 72W

• 35 mm DIN-Rail Mountable