beautypg.com

Nvironment, Rotection, Eatures – B&B Electronics NTPS-48-5 - Datasheet User Manual

Page 11: 48v, 5a, s

background image

CS10.481

CSeries

48V, 5A, S

INGLE

P

HASE

I

NPUT

Nov. 2006 / Rev.1.1 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

www.pulspower.com Phone +49 89 9278 0 Germany

11/20

15. E

NVIRONMENT

Operational temperature

-25°C to +70°C (-13°F to 158°F)

reduce output power according

Fig. 15-1

Output de-rating

3.2W/°C

45-60°C (113°F to 140°F)

6W/°C

60-70°C (140°F to 158°F)

Storage temperature

-40 to +85°C (-40°F to 185°F)

storage and transportation

Humidity

5 to 95% r.H.

IEC 60068-2-30

Do not energize while condensation is present

Vibration sinusoidal

2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis

IEC 60068-2-6

Shock

30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total

IEC 60068-2-27

Altitude

0 to 6000m (0 to 20 000ft)

Reduce output power or ambient
temperature above 2000m sea level.

Output de-rating (for altitude)

15W/1000m or 5°C/1000m

above 2000m (6500ft), see

Fig. 15-2

Over-voltage

category

III

EN

50178, altitudes up to 2000m

II

Altitudes from 2000m to 6000m

Degree of pollution

2

EN 50178, not conductive

Fig. 15-1 Output current vs. ambient temp.,

Fig. 15-2 Output current vs. altitude

Allowable Output
Current at 48V

0

-25

0

20

40

70°C

1

2

3

4

5

6A

60

Ambient Temperature

continuous

short

term

0

0

2000

4000

6000m

1

2

3

4

5

6A

Altitude

A... Tamb < 60°C

B... Tamb < 50°C
C... Tamb < 40°C

C

B

A

short term

Allowable Output
Current at 48V

The ambient temperature is defined 2cm below the unit.

16. P

ROTECTION

F

EATURES

Output

protection

Electronically protected against overload, no-load and short-circuits

Output over-voltage protection

typ. 56Vdc
max. 60Vdc

In case of an internal power supply defect, a redundant
circuitry limits the maximum output voltage. The output
shuts down and automatically attempts to restart.

Output over-current protection electronically

limited see

Fig. 8-1

Degree of protection

IP 20

EN/IEC 60529

Penetration protection

> 3.5mm

e.g. screws, small parts

Over-temperature

protection

yes

output shut-down with automatic restart

Input transient protection

MOV

Metal Oxide Varistor

Internal input fuse

T6.3A H.B.C.

not user replaceable

Note: In case of a protection event, audible noise may occur.