beautypg.com

Step immunity and no r, Sense – Rainbow Electronics MAX5937 User Manual

Page 20

background image

MAX5936/MAX5937

-48V Hot-Swap Controllers with V

IN

Step Immunity and No R

SENSE

20

___________________________________________________

Verification of the Step

Monitor Timing

It is prudent to verify conclusively that all circuit-breaker
and short-circuit faults will be blocked for all ramp
rates. To do this, some form of graphical analysis is
recommended but first, find the value of τ

L,eqv

of the

load by a series of ramp tests as indicated earlier.
These tests include evaluating the load with a series of
V

IN

ramps of increasing ramp rates and monitoring the

rate of V

OUT

rise during the ramp. Each V

IN

ramp

should have a constant slope. The V

OUT

response data

must be taken only during the positive ramp. Data
taken after V

IN

has leveled off at the new higher value

must not be used.

Figure 18 shows the load in parallel with the load
capacitor, C

LOAD

, and the parallel connection in series

with the power MOSFET, which is fully enhanced with
V

GS

= 10V. The objective is to determine τ

L,eqv

from

the V

OUT

response.

Figure 19 shows the general response of V

OUT

to a V

IN

ramp over time t. Equation 1 gives the response of V

OUT

to a ramp of dV/dt. The product (dV/dt) x τ

C

=

∆V

OUT

(max) or the maximum V

OUT

voltage differential if

the V

IN

ramp were to continue indefinitely. The parame-

ter of interest is ∆V

OUT

due to the ramp dV/dt, thus it is

necessary to subtract the DC shift in V

OUT

due to the

load resistance. For some loads, which are relatively
independent of supply voltage, this may be insignificant.

V

OUT

(t) = V

OUT

(t) - R

DS(ON)

x I

LOAD

where I

LOAD

is a function of the V

OUT

level that should

be determined separately with DC tests.

At any time (t) the ∆V

OUT

fraction of ∆V

OUT

(max) is:

∆V

OUT

(t) / [(dV/dt) x τ

C

] = (1-e

(-t / τL,eqv)

)

If V

OUT

(t) is measured at time t, then the equivalent

time constant of the load is found from:

τ

L,eqv

= -t / ln(1 - ∆V

OUT

/ [(dV/dt) x τ

C

])

As mentioned earlier, several measurements of ∆V

OUT

at times t1, t2, t3, and t4 should be made during the
ramp. Each of these may result in slightly different val-
ues of τ

L,eqv

and all values should then be averaged.

In making the measurements, the V

IN

ramp duration

should be such that ∆V

OUT

reaches 2 or 3 times the

selected ∆V

SC

. The ramp tests should include three

ramp rates: ∆V

SC

/ τ

C

, 2 x ∆V

SC

/ τ

C

and 4 x ∆V

SC

/ τ

C

.

The values of τ

L,eqv

may vary over the range of slew

rates due to measurement error, nonlinear dynamics in
the load, and due to the fact that Equation 1 is a simpli-
fication from a higher order dynamic system. The
resulting range of τ

L,eqv

values should be used to vali-

date the performance of the final design.

Having τ

C

, τ

L,eqv

, R

STEP

, and C

STEP

in a graphical

analysis using Equation 1 and Equation 2 can verify the
step monitor function by displaying the relative timing
of t

CB

, t

STEP

, and t

SC

, which are the times when V

CB

,

V

STEP_MON

, and V

SC

voltage thresholds are exceeded.

A simple spreadsheet for this purpose can be supplied
by Maxim upon request. Figures 20, 21, and 22 graphi-
cally verify a particular solution over 3 decades of V

IN

ramp rates. In addition, Figure 22 verifies that this solu-
tion will block all circuit-breaker and short-circuit faults
for even the lowest V

IN

ramp that will cause V

OUT

to

exceed V

CB

.

Figure 18. V

IN

Ramp Test of Load

L

EQU

R

EQV

C

LOAD

LOAD

LOAD CAPACITOR
WITH PARASITICS

V

IN

RAMP

10V

R

DS,ON

Figure 19. General Response of V

OUT

to a V

IN

Ramp

dv

dt

τ

C

dv

dt

V

IN

VOUT.F

VOUTi

V

IN

RAMP

0

t1

t2

t3

t4