beautypg.com

Operation – Grain Systems Bucket Elevtors, Conveyors, Series II Sweeps PNEG-1366 User Manual

Page 31

background image

5. Assembly

PNEG-1366 12" and 16" Series II Sweep Quick Disconnect Control Box Kit

31

Operation

1. Setting Presets

a. Press “Pre A”.

b. Press “PRGM”

This value = “High Amp Set Point”.

Use arrow buttons to change value.

c. Press “ENTER”.

2. Setting Relays

a. Press “PRGM” to “rELAYS”.

b. Press “ENTER” to “HYS A”.

c. Press “PRGM”

This value = “High Amp Set Point”-“Low Amp Set Point”

Use arrow buttons to change value.

d. Press “ENTER” to RUN MODE.

EXAMPLE: Full Load Running Amps = 21 Amps

High Amp Set Point = 20 Amps

Low Amp Set Point = 12 Amps

Then “HYS A” = 8 Amps

And “Pre A” = 20 Amps

NOTE: This is the difference between the High Amp Set Point and the Low Amp Set Point.

[20 Amps-12 Amps = 8 Amps]. Low amp set point is only used to calculate this value.

3. Locking the Amp Meter

1. Locking the Amp meter is not required but prevents the meter from being tampered with once it

is programmed.

2. In RUN MODE, press “LOCK” three (3) times within five (5) seconds.

This value = A number that is easily remembered.

Use arrow buttons to change value.

a. Press “ENTER”.

4. Unlocking the Amp Meter

1. In RUN MODE, press “LOCK” three (3) times within five (5) seconds.

a. Enter the “LoC” value.

Use arrow buttons to change value.

b. Press “ENTER”.

NOTE: It is recommended to write down the “LoC” value and keep it in a safe place in case it

is forgotten.