Grain Systems Bucket Elevtors, Conveyors, Series II Sweeps PNEG-1366 User Manual
Page 29
5. Assembly
PNEG-1366 12" and 16" Series II Sweep Quick Disconnect Control Box Kit
29
If you select NO, press OK.
If you select YES, N.PAS will be displayed. Press
or
on the display unit until your password is shown.
Press OK. Document this password.
The password will be necessary if there needs to be changes to many of the configuration values.
If the meter looks like this:
Figure 5J
Follow these instructions:
NOTE: In order to fine tune the control panel, the bin must have grain in it.
The Series II Sweep is supplied with adjustable overloads that are not set at the factory. These should be
set slightly higher than the Full Load Amp (FLA) value listed on the motor nameplates.
A. Find the desired “High” Amp and “Low” Amp set points.
1. High Amp Set Point: The Amp load the auger draws when the auger flighting is 90% loaded.
This will turn OFF the tractor drive motor. Initially, set the value to 90% of the Full Load Amps
(FLA) listed on the motor nameplate.
2. Low Amp Set Point: The Amp load the auger motor draws when the auger flighting is 10%
loaded. This will turn ON the drive motor. Initially, set this value to 10% over the Amp draw of the
sweep running empty.
B. Programming the Amp Meter.
NEVER program the “High Amp Set Point” greater than the full load running
Amps of the auger motor.