beautypg.com

Final display setup – Grain Systems Bucket Elevtors, Conveyors, Series II Sweeps PNEG-1597 User Manual

Page 25

background image

5. Operation

PNEG-1597 Sweep Tractor and Control Panel Assembly Instructions

25

Final Display Setup

NOTE: If no keys are activated for 2 minutes, the display returns to the default state without saving any

configuration changes. At each value, after 5 seconds of inactivity, a description of the current
state will scroll across the display.

Press OK repeatedly until RELU is displayed on the unit.

Press

or

on the display unit until DISP is shown (not PERC).

Press OK.

REL1 should be displayed on the unit.

Press

or

on the display unit until SET is shown (not SKIP or OFF).

Press OK.

SETP should be displayed on the unit.

Press

or

on the display unit the 90% of FLA value is shown.

Press OK.

ACT1 should be displayed on the unit.

Press

or

on the display unit until INCR is shown (not DECR).

Press OK.

HYS1 should be displayed on the unit.

For this control panel hysteresis (HYS1) is measured as the different between 90% of full load amps and
110% of no load amps.

90% of full load amps: ____ minus 110% of no load amps: ____

Press

or

on the display unit until the correct value is shown.

Press OK.

ERR1 should be displayed on the unit.

Press

or

on the display unit until DEAC is shown (not HOLD, ACTI or NONE).

Press OK.

ON.DE should be displayed on the unit.

Press

or

on the display unit until 0 is shown.

Press OK.