For va – Grain Systems PNEG-1798 User Manual
Page 23

7. Procedure
PNEG-1798 Tower and T-Series Dryers Vaporizer
23
Figure 7Q Piping Exiting the Window using U-Bolts and Support Brackets
7.3.7. Vaporizer piping (3/4" and 1-1/4") continues downward through the piping window opening and
then vertically and in parallel with the 2" burner supply line toward the gas train.
7.3.8. Continue piping (3/4" and 1-1/4") downward to the gas train. Anchor the vertical run piping in at
least two (2) locations on the outside of the dryer. Uni-strut and clamps are commonly used for this.
7.3.9. Connect the 3/4" vaporizer line to the gas train liquid supply line. This will allow this section of the
gas train supply piping and associated components to be pressure tested in
.
7.3.10. Install a 2" to 1/4" reducing bushing at the end of the 2" to 1-1/4" bell reducer for the connection
of a test gauge. Some test gauges may have a 3/8" MNPT fitting, if so reduce down to allow a for
the test gauge connection size.
7.3.11. Install the 0-300 PSIG test gauge at the reducer bushing fitting of the preceding step. Verify this
gauge has a 0 PSIG reading.
7.3.12. Proceed to vaporizer high pressure leak testing