beautypg.com

Technical data – Milton CAT D50-6 50 kW Spec Sheet User Manual

Page 4

background image

STANDBY 50 ekW 63 kVA

PRIME 45 ekW 50 kVA

60 Hz 1800 rpm 480 Volts

TECHNICAL DATA

Open Generator Set – 1800 rpm/60 Hz/480 Volts

P3454A

P3454B

Tier 3

Standby

Prime

Generator Set Package Performance
Genset power rating @ 0.8 pf
Genset power rating with fan

62.5 kVA

50.0 ekW

56,3 kVA

45.0 ekW

Fuel Consumption
100% load with fan
75% load with fan
50% load with fan

16.8 L/hr
12.8 L/hr
9.3 L/hr

4.4 Gal/hr
3.4 Gal/hr
2.5 Gal/hr

15.2 L/hr
11.7 L/hr
8.7 L/hr

4.0 Gal/hr
3.1 Gal/hr
2.3 Gal/hr

Cooling System

1

Air flow restriction (system)
Engine coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity

0.12 kPa
1.5 L
7.0 L
9.5 L

0.48 in. water
4.4 gal
1.8 gal
2.5 gal

0.12 kPa
1.5 L
7.0 L
9.5 L

0.48 in. water
4.4 gal
1.8 gal
2.5 gal

Inlet Air
Combustion air inlet flow rate

5.3 m³/min

187.2 cfm

5.2 m³/min

183.6 cfm

Exhaust System
Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system back pressure (maximum)

571°C
13.7 m³/min
63.5 mm
15.0 kPa

1060°F
483.8 cfm
2.5 in
60.2 in. water

532°C
12.8 m³/min
63.5 mm
15.0 kPa

990°F
452.0cfm
2.5 in
60.2 in. water

Heat Rejection
Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator

46.1 kW
66.9 kW
14.9 kW
4.4 kW

2622 Btu/min
3805 Btu/min
847.3 Btu/min
250.2 Btu/min

42.3kW
59.3 kW
12.5 kW
3.8 kW

2406 Btu/min
3372 Btu/min
710.9 Btu/min
216.1 Btu/min

Alternator

2

Motor starting capability @ 30% voltage dip
Frame
Rotor temperature rise

157 skV
LC1514P
105°C

189°F

157 skV
LC1514P
80°C

144°F

Lubrication System
Total oil capacity
Oil pan

8.4 L
6.9 L

2.2 gal
1.8 gal

8.4 L
6.9 L

2.2 gal
1.8 gal

1

For ambient and altitude capabilities consult your Cat dealer. Airflow restriction (system) is added to existing restriction from factory.

2

Generator temperature rise is based on a 40°C (104°F) ambient per NEMA MG1-32.

4