STARTING CAPABILITIES (sKVA)
FUEL
Natural Gas
Three-Phase 120/208VAC @0.8pf
230
Amps: 799
Three-Phase 120/240VAC @0.8pf
230
Amps: 692
Three-Phase 277/480VAC @0.8pf
230
Amps: 346
Three-Phase 346/600VAC @0.8pf
230
Amps: 277
sKVA vs. Voltage Dip
480VAC
208/240VAC
Alternator
kW
10%
15%
20%
25%
30%
35%
10%
15%
20%
25%
30%
35%
Standard
230
263
395
527
658
790
922
197
296
395
494
593
692
Upsize 1
300
303
454
605
757
908
1059
227
341
454
568
681
794
COOLING
COMBUSTION AIR REQUIREMENTS
ENGINE
EXHAUST
Flow at Rated Power
cfm
408
Rated Engine Speed
rpm
1800
Horsepower at Rated kW**
hp
368
Piston Speed
ft/min
1773
BMEP
psi
206
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
Exhaust Flow (Rated Output)
cfm (m
3
/min)
1442 (40.8)
Maximum Recommended Back Pressure
inHg
1.5
Exhaust Temp (Rated Output)
ºF (ºC)
1446 (786)
Exhaust Outlet Size (Catalyst)
in
5.0"
POWER RATINGS (kW)
Fuel Consumption Rates*
Natural Gas
Percent Load
ft
3
/min
ft
3
/hr
m
3
/hr
25%
17.5
1050
29.7
50%
26
1560
44.2
75%
33.7
2022
57.3
100%
43.1
2586
73.2
* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and
SCAQMD permitting purposes.
Air Flow (inlet air combustion and radiator)
ft
3
/min (m
3
/min)
10,078 (285.4)
System Coolant Capacity
Gal (Liters)
19 (71.9)
Heat Rejection to Coolant
BTU/hr
743,830
Max. Operating Air Temp on Radiator
ºF (ºC)
122 (50)
Max. Ambient Temperature
ºF (ºC)
104 (40)
Maximum Radiator Backpressure
in H
2
O
0.5
3 of 5
G230LG
operating data (60Hz)
G230LG 230kW
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.