ENGINE SPECIFICATIONS

General

Cooling System

Make

Generac

Cooling System Type

Pressurized Closed Recovery

EPA Emissions Compliance

Stationary Emergency

Water Pump Flow

79 gal/min

EPA Emissions Engine Reference

See Emissions Data Sheet

Fan Type

Pusher

Cylinder #

6

Fan Speed (rpm)

1894

Type

Inline

Fan Diameter mm (in.)

762 (30)

Displacement - L

12.88

Coolant Heater Wattage

2000

Bore - mm (in.)

135 (5.31)

Coolant Heater Standard Voltage

240VAC

Stroke - mm (in.)

150 (5.91)

Compression Ratio

10.92:1

Intake Air Method

Turbocharged/Aftercooled

Number of Main Bearings

7

Fuel System*

Connecting Rods

Carbon Steel

Fuel Type

Natural Gas

Cylinder Head

Cast Iron HT250, OHV

Carburetor

Down Draft

Cylinder Liners

Ductile Iron

Secondary Fuel Regulator

Standard

Ignition

Altronic CD1

Fuel Shut Off Solenoid

Standard

Pistons

Aluminum

Operating Fuel Pressure

11" - 15" H

2

O

Crankshaft

Ductile Iron

Lifter Type

Solid

*Fuel pressure must remain within specified range and not drop more than 1
in. w.c. from static (no-load) to full load.

Intake Valve Material

Special Heat-Resistant Steel

Exhaust Valve Material

Alloy Steel, High Temp

Hardened Valve Seats

Alloy Steel, High Temp

Engine Electrical System
System Voltage

24VDC

Lubrication System

Battery Charging Alternator (Amps)

Std

Oil Pump Type

Gear

Battery Size

1155 CCA

Oil Filter Type

Full-flow cartridge

Battery Group

8D

Crankcase Capacity - L (qts)

34.3 (36.4)

Battery Voltage

(2) 12VDC

Ground Polarity

Negative

ALTERNATOR SPECIFICATIONS

Standard Model

520

Voltage Regulator Type

Full Digital

Poles

4

Number of Sensed Phases

3

Field Type

Revolving

Regulation Accuracy (Steady State)

+/- 0.25%

Insulation Class - Rotor

H

Insulation Class - Stator

H

Total Harmonic Distortion

<5%

Engine Governing

Telephone Interference Factor (TIF)

<50

Governor

Electronic

Standard Excitation

Permanent Magnet

Frequency Regulation (Steady State)

+/- 0.25%

Bearings

Sealed Ball

Coupling

Direct, Flexible Disc

Load Capacity - Standby

230kW

Prototype Short Circuit Test

Yes

CODES AND STANDARDS COMPLIANCE (WHERE APPLICABLE)

NFPA 99

BS5514

NFPA 110

SAE J1349

ISO 8528-5

DIN6271

ISO 1708A.5

IEEE C62.41 TESTING

ISO 3046

NEMA ICS 1
UL2200

2 of 5

G230LG

application and engineering data

G230LG 230kW