Milton CAT C15 Factory Integral Fuel Tank Base User Manual
C15 integral fuel tank base, Features description, Options
FEATURES
DESCRIPTION
A T T A C H M E N T S
C15 INTEGRAL
FUEL TANK BASE
Diesel Generator Set
400 – 550 kVA 50 Hz
350 – 550 kW 60 Hz
●
UL 142 listed
●
Designed and built to comply with
NFPA 30, 37, 110
●
Direct reading fuel level gauge
●
Primary tank leak detection switch in
containment basin
●
Fuel fill – 101.6 mm (4 in), lockable cap
●
Supply and return ports equipped with dip tubes
●
Additional capacity at top to contain spillage
●
Additional capacity at bottom to (weather
protective and sound sediment pickup)
●
Internally baffled to separate supply and return
fuel ports
●
Primary tank atmospheric vent – 50.8 mm (2 in)
NPT with cap and screen
●
Interior tank surfaces coated with a solvent-based,
thin-file rust preventative
●
Welded steel containment basin (minimum of
110% of primary tank capacity)
●
Tank designed to contain coolant and engine
oil spills
●
High performance, gloss black, alkyd acrylic
enamel exterior paint over epoxy based primer
●
Heavy
1
⁄
4
" steel construction primary (inner) tank
and side channels
●
Integral diesel fuel tank is incorporated into the
generator set base frame.
●
Robust base design includes linear vibration
isolators between tank base and engine-
generator.
●
Emergency vent on primary and secondary tanks
are sized in accordance with NFPA 30.
●
Dual wall.
●
Primary and secondary tanks are leak tested
at 20.7 kPa (3 psi) minimum.
●
Compatible with enclosures (weather protective
and sound attenuated).
OPTIONS
●
Manual fuel transfer pump
●
Auto fuel transfer system
– Below grade main tank (pumped supply/
gravity return)
– Elevated main tank (gravity supply)
– Pumped supply from free standing
●
Low fuel level switch (alarm/shutdown)
LEHE5511-00