STANDBY 500 ekW 625 kVA

60 Hz 1800 rpm 480 Volts

FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT

System

Standard

Optional

Air Inlet

• Light Duty Air filter

• Canister Style Air Cleaners
• Air Cleaner - single stage
• Dual element
• Heavy duty

Cooling

• Radiator package mounted(50ºC)
• Coolant drain line with valve terminated at edge of

base

• Fan and belt guards
• Coolant level sight gauge
• Caterpillar Extended Life Coolant

• Radiator removal
• Radiator duct flange & guard

Exhaust

• Dry exhaust manifold
• Flanged faced outlets
• Stainless Steel Flex with split-cuff connection

• Mufflers
• Manifold & Turbocharger guards
• Elbows

Fuel

• Primary fuel filter with integral water separator
• Secondary fuel filters
• Fuel priming pump
• Engine fuel transfer pump
• Flex fuel lines
• Fuel cooler*
*Not included with packages without radiators

• Integral UL listed fuel tank base
• Manual transfer pump
• Fuel level switch

Generator

• Class H insulation
• R448 voltage regulator with load adjustment module
• IP23 Protection

• CDVR with KVAR/PF control
• Oversize and premium generators
• Bearing/Stator temperature detection (premium

generator)

• 3 phase sensing
• Anti-condensation space heaters
• Cable access box
• Reactive droop

Power Termination

• Power Terminator Strips Mounted inside Power

Center

• Segregated low voltage wiring panel

• Circuit breakers, UL listed, 3 pole
• Circuit breakers, IEC compliant, 3 pole
• Circuit breaker Shunt trip
• Circuit breaker Auxillary contact
• Top & bottom power cable entry
• Floor standing UL breakers

Governor

• ADEM™A4

• Load share module

Control Panels

• EMCP 3.1 (rear mounted)
• Speed adjust
• Emergency stop pushbutton
• Voltage adjust

• EMCP 3.2 & EMCP 3.3 (can be RH mounted)
• Local annuniciator modules (NFPA 99/110)
• Remote annunicator modules (NFPA 99/110)
• Discrete I/O module

Lube

• Lubricating oil and filter
• Oil drain line with valves
• Fumes disposal
• Gear type lube oil pump

• Manual sump pump

Starting/Charging

• 24 volt starting motor
• Battery with rack and cables (dry)
• 45 amp charging alternator

• Jacket water heater with shut off valves
• Block heater
• Ether starting aids
• Battery disconnect switch
• Battery chargers ( 5 & 10 amp)
• Oversized batteries

General

• Paint - Caterpillar yellow except rails and radiators

gloss black

• Flywheel and flywheel housing - SAE No.1

May 04 2009 13:45 PM