Technical data – Milton CAT 3516C HD 2500 kW 3125 kVA 60 Hz 1800 rpm 480 Volts Spec Sheet User Manual
Page 4

®
STANDBY 2000 ekW 2500 kVA
60 Hz 1800 rpm 480 Volts
TECHNICAL DATA
Open Generator Set - - 1800 rpm/60 Hz/480 Volts
DM8263
EPA Tier 2
Generator Set Package Performance
Genset Power rating @ 0.8 pf
Genset Power rating with fan
2500 kVA
2000 ekW
Coolant to aftercooler
Coolant to aftercooler temp max
50 ° C
122 ° F
Fuel Consumption
100% load with fan
75% load with fan
50% load with fan
525.7 L/hr
138.9 Gal/hr
408.2 L/hr
107.8 Gal/hr
294.2 L/hr
77.7 Gal/hr
Cooling System
1
Ambient air temperature
Air flow restriction (system)
Air flow (max @ rated speed for radiator arrangement)
Engine Coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity
46 ° C
115 ° F
0.12 kPa
0.48 in. water
2480 m³/min
87580 cfm
475.0 L
125.5 gal
233.0 L
61.6 gal
242.0 L
63.9 gal
Inlet Air
Combustion air inlet flow rate
180.3 m³/min
6367.2 cfm
Exhaust System
Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system backpressure (maximum allowable)
405.4 ° C
761.7 ° F
428.6 m³/min
15135.9 cfm
203.2 mm
8.0 in
6.2 kPa
24.9 in. water
Heat Rejection
Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to aftercooler
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator
765 kW
43505 Btu/min
1804 kW
102593 Btu/min
666 kW
37875 Btu/min
137 kW
7791 Btu/min
74.7 kW
4248.2 Btu/min
Alternator
2
Motor starting capability @ 30% voltage dip
Frame
Temperature Rise
4647 skVA
825
130 ° C
266 ° F
Lube System
Sump refill with filter
401.3 L
106.0 gal
Emissions (Nominal)
3
NOx g/hp-hr
CO g/hp-hr
HC g/hp-hr
PM g/hp-hr
5.39 g/hp-hr
.29 g/hp-hr
.11 g/hp-hr
.026 g/hp-hr
1
Ambient capability at 300 m (984ft) above sea level. For ambient capability at other altitudes, consult your Caterpillar dealer.
2
UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator
temperature rise is based on a 40 degree C ambient per NEMA MG1-32.
3
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77°F, 28.42 in HG and number 2 diesel fuel
with 35° API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and
engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use
values based on a weighted cycle.
1 May 2006