S T A N D B Y 1 7 5
k W
P R I M E 1 5 7 . 5
k W
6 0 H z
LEHE6275-05
5
D175-2 (3-Phase)
Materials and specifications are subject to change without notice.
Generator Set Technical Data — 1800 rpm/60 Hz
Standby
Prime
Power Rating*
kW
kVA
175
218.8
157.5
196.9
Lubricating System
Type: Full Pressure
Oil Filter: Spin-On, Full Flow
Oil Cooler: Watercooled
Oil Type Required: API CH-14; API-C15
Total Oil Capacity
L
U.S. gal
16.5
4.4
16.5
4.4
Oil Pan
L
U.S. gal
15.5
4.1
15.5
4.1
Fuel System
Generator Set Fuel Consumption
100% Load
L/hr
G/hr
53.8
14.2
50.2
13.3
75% Load
L/hr
G/hr
43.7
11.5
41.2
10.9
50% Load
L/hr
G/hr
34.7
9.2
33.3
8.8
Engine Electrical System
Voltage/Ground: 12V/Ground
Battery Charging Generator Ampere Rating
Amps
100
101
Cooling System
Water Pump Type: Centrifugal
Radiator System Capacity Incl. Engine
L
U.S. gal
21.0
5.5
21.0
5.5
Maximum Coolant Static Head
m H
2
O
ft H
2
O
8.0
26.0
8.0
26.0
Coolant Flow Rate
L/hr
U.S. gal/hr
12 960
3,424
12 960
3,424
Minimum Temperature to Engine
°C
°F
85
185
85
185
Temperature Rise Across Engine
°C
°F
9
14.2
9
14.2
Heat Rejected to Coolant at Rated Power
kW
Btu/min
93.5
5,322
86.8
4,941
Total Heat Radiated to Room at Rated Power
kW
Btu/min
16.2
922
14.9
848
Radiator Fan Load
kW
hp
15
20.12
15
20.12
Air Requirements
Combustion Air Flow
m
3
/min
cfm
12.6
445
12.3
434.4
Maximum Air Cleaner Restriction
kPa
in H
2
O
8
32
8
32
Radiator Cooling Air (zero restriction)
m
3
/min
cfm
30
15,171
30
15,171
Generator Cooling Air
m
3
/min
cfm
30.6
1,081
30.6
1,081
Allowable Air Flow Restriction (after radiator)
kPa
in H
2
O
0.12
0.5
0.12
0.5
Cooling Airflow (@ rated speed)
Rate with restriction
m
3
/min
cfm
390
13,773
390
13,773
Exhaust System
Maximum Allowable Backpressure
kPa
in Hg
15.0
4.4
15.0
4.4
Exhaust Flow at Rated kW
m
3
/min
cfm
29.7
1,049
28.6
1,010
Exhaust Temperature at Rated kW —
Dry Exhaust
°C
°F
677
1251
666
1231
Generator Set Noise Rating**
(Without Attenuation) at 1 m (3 ft)
dB(A)
100.6
100.6
*
*Three phase power rating
**dBA levels are for guidance only
277/480V
266/460V
127/220V
120/240V
347/600V
Generator Technical Data
120/208V
Motor Starting Capability: (kVA)
(30% voltage dip)
Self excited
454
422
392
355
N/A
PM excited**
543
506
469
425
506
AREP excited
543
506
469
425
506
Full Load Efficiencies:
Standby
93.0
93.0
92.9
92.6
93.0
Prime
93.1
93.2
93.1
92.8
93.0
Reactances (per unit):
X
d
2.74
2.99
3.26
3.65
2.99
X'
d
0.13
0.15
0.16
0.18
0.15
X"
d
0.081
0.088
0.096
0.108
0.088
X
q
1.64
1.79
1.96
2.19
1.79
X"
q
0.100
0.109
0.119
0.133
0.109
X
2
0.090
0.098
0.107
0.120
0.098
X
0
0.005
0.005
0.005
0.006
0.005
Time Constants:
t'
d
t"
d
t'
do
t
a
100 ms
10 ms
2865 ms
15 ms
Reactances
shown are
applicable to the
standby rating.