Rating definitions, Specifications – Milton CAT G175 LG4 Spec Sheet User Manual

Page 4

background image

S T A N D B Y 1 7 5

k W

P R I M E 1 5 7 . 5

k W

6 0 H z

LEHE6275-05

4

Standby — Applicable for supplying continuous electrical
power (at variable load) in the event of a utility power
failure. No overload is permitted on these ratings.
The generator is peak rated (as defined in ISO8528-3).

Prime — Applicable for supplying continuous electrical
power (at variable load) in lieu of commercially purchased
power. There is no limitation to the annual hours of
operation and the generator set can supply 10 percent
overload power for 1 hour in 12 hours.

RATING DEFINITIONS

GENERATOR

Voltage Regulation..................... ±0.5% 3-phase at steady state

from no load to full load

Frequency............................................±0.25% for constant load,

no load to full load

Waveform Distortion ..................................THD <4%, at no load
Radio Interference .........................Compliance with EN61000-6
Telephone Interference ....................................TIF <50, THF <2%
Overspeed Limit.............................................................2250 rpm
Insulation .......................................................................... Class H
Temperature Rise ...................................... Within Class H limits
Available Voltages ............................ 277/480, 266/460, 120/240,

127/220, 120/208, 347/600

Deration ......................................... Consult factory or Specsizer
Ratings ................................... At 30° C (86° F), 152.4 m (500 ft),

60% humidity, 0.8 pf (3-Phase)

ENGINE

Manufacturer ............................................................... Caterpillar
Type .................................................................................. 4-Cycle
Bore — mm (in) ........................................................ 105.0 (4.13)
Stroke — mm (in) ....................................................... 127.0 (5.0)
Governor Type ............................................................. Electronic
Class .......................................................................................... G2
Piston Speed — m/secf (t/sec) ................................... 7.62 (25.0)
Engine speed — rpm............................................................ 1800
Air Cleaner Type ..................................... Dry, replaceable paper

element type with restriction indicator

D175.2 — C6.6 ACERT
Aspiration .......................................................................... ATAAC
Cyliner Configuration ..................................................... In-line 6
Displacement — L(in

3

)................................................. 6.6 (402.7)

Compression ratio .............................................................. 16.3:1
Maximum Power at rated rpm — kW (hp)

Standby ................................................................ 204.3 (273.9)
Prime .................................................................... 185.7 (249.0)

BMEP — kPa (psi)

Standby ................................................................. 2065 (299.5)
Prime ..................................................................... 1877 (272.2)

Regenerative power — kW (hp)................................. 14.9 (19.9)

CONTROL PANEL

Heavy duty sheet steel enclosure with lockable hinged door

Vibration isolated from generating set

LCD display

AC metering

DC metering

Fail to start shutdown

Low oil pressure shutdown

High engine temperature

Low/high battery voltage

Underspeed/overspeed

Loss of engine speed detection

2 spare fault channels

20 event fault log

2 LED status indicators

Lockdown emergency stop push button

SPECIFICATIONS