Technical data – Milton CAT C32 1000 kW 1250 kVA 60 Hz 1800 rpm 480 Volts Spec Sheet User Manual
Page 4

®
STANDBY 1000 ekW 1250 kVA
60 Hz 1800 rpm 480 Volts
TECHNICAL DATA
Open Generator Set - - 1800 rpm/60 Hz/480 Volts
DM9933
EPA Certified Tier 2
Generator Set Package Performance
Genset Power rating @ 0.8 pf
Genset Power rating with fan
1250 kVA
1000 ekW
Coolant to aftercooler
Coolant to aftercooler temp max
49 º C
120 º F
Fuel Consumption
100% load with fan
75% load with fan
50% load with fan
272.5 L/hr
72.0 Gal/hr
213.2 L/hr
56.3 Gal/hr
144.7 L/hr
38.2 Gal/hr
Cooling System
1
Air flow restriction (system)
Air flow (max @ rated speed for radiator arrangement)
Engine Coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity
0.12 kPa
0.48 in. water
1126 m³/min
39764 cfm
190.0 L
50.2 gal
55.0 L
14.5 gal
135.0 L
35.7 gal
Inlet Air
Combustion air inlet flow rate
86.9 m³/min
3068.8 cfm
Exhaust System
Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system backpressure (maximum allowable)
478.5 º C
893.3 º F
230.2 m³/min
8129.4 cfm
203 mm
8 in
10.0 kPa
40.2 in. water
Heat Rejection
Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to aftercooler
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator
355 kW
20189 Btu/min
988 kW
56187 Btu/min
279 kW
15867 Btu/min
196 kW
11146 Btu/min
56.0 kW
3184.7 Btu/min
Alternator
2
Motor starting capability @ 30% voltage dip
Frame
Temperature Rise
1990 skVA
692
130 º C
234 º F
Lube System
Sump refill with filter
68.0 L
18.0 gal
Emissions (Nominal)
3
NOx g/hp-hr
CO g/hp-hr
HC g/hp-hr
PM g/hp-hr
4.93 g/hp-hr
.13 g/hp-hr
.01 g/hp-hr
.018 g/hp-hr
1
For ambient and altitude capabilities consult your Caterpillar dealer. Air flow restriction (system) is added to existing restriction from
factory.
2
UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator
temperature rise is based on a 40ºC ambient per NEMA MG1-32.
3
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77ºF, 28.42 in HG and number 2 diesel fuel
with 35º API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine
to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values
based on a weighted cycle.
September 02 2009 14:28 PM
4
SS-006378.pdf: Secured on 09/03/2009 02:17