beautypg.com

Specifications – Milton CAT C32 1000 kW 1250 kVA 60 Hz 1800 rpm 480 Volts Spec Sheet User Manual

Page 3

background image

®

STANDBY 1000 ekW 1250 kVA

60 Hz 1800 rpm 480 Volts

SPECIFICATIONS

CAT GENERATOR

SR4B Generator

Frame size......................................................................... 692

Excitation.............................................................Self Excited

Pitch.............................................................................. 0.7143

Number of poles................................................................... 4

Number of bearings............................................................. 2

Number of Leads................................................................ 12

Insulation....................... UL 1446 Recognized Class H with

tropicalization and antiabrasion
IP rating..........................................................Drip Proof IP22

Alignment....................................................... Close Coupled

Overspeed capability - % of rated................................... 150

Wave form....................................................................003.00

Voltage regulator.3 Phase sensing with selectible volts/Hz

Voltage regulation............Less than +/- 1/2% (steady state)

Less than +/- 1% (no load to full load)
Telephone Influence Factor.............................. Less than 50

Harmonic distortion......................................... Less than 5%

CAT DIESEL ENGINE

C32 TA, V-12, 4-stroke watercooled diesel

Bore - mm.............................................. 145.00 mm (5.71 in)

Stroke - mm........................................... 162.00 mm (6.38 in)

Displacement - L................................... 32.10 L (1958.86 in

3

)

Compression ratio........................................................ 15.0:1

Aspiration........................................................................... TA

Fuel system....................................................................MEUI

Governor type..................................................... ADEM™ A4

CAT EMCP 3 SERIES CONTROLS

• EMCP 3.1 (Standard)

• EMCP 3.2 / EMCP 3.3 (Option)

• Single location customer connector point

• True RMS metering, 3-phase

• Controls

- Run / Auto / Stop control

- Speed Adjust

- Voltage Adjust

- Emergency Stop Pushbutton

- Engine cycle crank

• Digital Indication for:

- RPM

- Operating hours

- Oil Pressure

- Coolant temperature

- System DC volts

- L-L volts, L-N volts, phase amps, Hz

- ekW, kVA, kVAR, kW-hr, %kW, PF (EMCP 3.2 / 3.3)

• Shutdowns with common indicating light for:

- Low oil pressure

- High coolant temperature

- Low coolant level

- Overspeed

- Emergency Stop

- Failure to start (overcrank)

• Programmable protective relaying functions: (EMCP 3.2

& 3.3)

- Under and over voltage

- Under and over frequency

- Overcurrent (time and inverse time)

- Reverse power (EMCP 3.3)

• MODBUS isolated data link, RS-485 half duplex (EMCP

3.2 & 3.3)
• Options

- Vandal door

- Local annunciator module

- Remote annunciator module

- Input / Output module

- RTD / Thermocouple Modules

- Monitoring software

September 02 2009 14:28 PM

3