beautypg.com

Specifications – Milton CAT 3512C 1500 kW 1875 kVA 60 Hz 1800 rpm 480 Volts Spec Sheet User Manual

Page 3

background image

®

STANDBY 1500 ekW 1875 kVA

60 Hz 1800 rpm 480 Volts

SPECIFICATIONS

CAT GENERATOR

SR4B Generator

Frame Size.........................................................................697

Excitation................................................ Permanent Magnet

Pitch.............................................................................. 0.7333

Number of poles................................................................... 4

Number of bearings...................................... Single Bearing

Number of Leads.................................................................. 6

Insulation....................... UL 1446 Recognized Class H with

tropicalization and antiabrasion
IP Rating.........................................................Drip Proof IP22

Alignment.............................................................. Pilot Shaft

Overspeed capability- % of rated.................................... 150

Wave form....................................................................003.00

Paralleling kit/Droop transformer.......................... Standard

Voltage Regulator3 Phase sensing with selectible volts/Hz

Telephone influence factor............................... Less than 50

CAT DIESEL ENGINE

3512C ATAAC, V-12, 4 stroke, water-cooled diesel

Bore........................................................ 170.00 mm (6.69 in)

Stroke..................................................... 190.00 mm (7.48 in)

Displacement.........................................51.80 L (3161.03 in

3

)

Compression Ratio....................................................... 14.7:1

Aspiration........................................................................... TA

Fuel System.................................... Electronic unit injection

Governor Type........................................................... ADEM3

CAT EMCP SERIES CONTROLS

• EMCP 3.1 (Standard)

• EMCP 3.2 / EMCP 3.3 (Option)

• Single location customer connector point

• True RMS AC metering, 3-phase

• Controls

- Run / Auto / Stop control

- Speed Adjust

- Voltage Adjust

- Emergency Stop Pushbutton

- Engine cycle crank

• Digital Indication for:

- RPM

- Operating hours

- Oil pressure

- Coolant temperature

- System DC volts

- L-L volts, L-N volts, phase amps, Hz

- ekW, kVA, kVAR, kW-hr, %kW, PF (EMCP 3.2 / 3.3)

• Shutdowns with common indicating light for:

- Low oil pressure

- High coolant temperature

- Low coolant level

- Overspeed

- Emergency stop

- Failure to start (overcrank)

• Programmable protective relaying functions: (EMCP 3.2

& 3.3)

- Under and over voltage

- Under and over frequency

- Overcurrent (time and inverse time)

- Reverse power (EMCP 3.3)

• MODBUS isolated data link, RS-485 half-duplex (EMCP

3.2 & 3.3)
• Options

- Vandal door

- Local annunciator module

- Remote annunciator module

- Input / Output module

- RTD / Thermocouple modules

- Monitoring software

May 27 2009 14:43 PM

3