AL1002ULADAJ
6. Connect FACP output to the desired AL800LGK logic board inputs, and notification appliances to the desired
AL800LGK logic board outputs (see Application Guide).
Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with
synchronization capability.
7. For connection of smoke detectors, digital dialer see Optional Hookup Diagram, pg. 7.
Class A, Style Z Class B, Style W, Y, SW1 & SW2 Settings:
• For all Class B, Style W, Y, hookups SW1 & SW2 on the AL800LGK logic board must be open.
For all Class A, Style Z hookups SW1 & SW2 on the AL800LGK logic board must be closed.
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Function
Switch Positions
Descriptions
ON
OFF
Input to Output Follower Mode
1
2, 3
Output follows signal it receives from the corresponding input
(i.e. FACP Sync module - maintains synchronization of
notification appliance circuit).
Temporal Code 3 Mode
3
1, 2
Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
Steady Mode
1, 2, 3
A steady output signal will be generated.
This mode will accept steady or pulsing input.
For the above modes Dip Switch 4 determines which Input controls
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Sync Mode Selection Table:
Function
Switch Positions
Descriptions
ON
OFF
Amseco Sync
Mode*
1, 3,
4
2
This mode is designed to work with the Amseco series of horns, strobes, and
horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the flash timing of the strobe, and silencing the horns of the horn/
strobe combination over a two-wire circuit while leaving strobes active.
Faraday
Sync Mode*
2, 4
1, 3
This mode is designed to work with the Faraday series of horns, strobes, and
horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the flash timing of the strobe, and silencing the horns of the horn/
strobe combination over a two-wire circuit while leaving strobes active.
Gentex
®
Sync Mode*
Gentex is a registered trademark
of Gentex Corporation.
1, 2,
3, 4
This mode is designed to work with the Gentex
®
series of horns, strobes, and
horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the flash timing of the strobe, and silencing the horns of the horn/
strobe combination over a two-wire circuit while leaving strobes active.
System Sensor
®
Sync Mode*
System Sensor is a registered
trademark of Honeywell.
1, 2, 4
3
This mode is designed to work with the System Sensor
®
series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the one-second flash timing of the strobe, and silencing the horns
of the horn/strobe combination over a two-wire circuit while leaving
strobes active.
CooperWheelock
®
Sync Mode*
CooperWheelock is a
registered trademark of
CooperWheelock.
2, 3, 4
1
This mode is designed to work with the CooperWheelock series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the one-second flash timing of the strobe, and silencing the horns
of the horn/strobe combination over a two-wire circuit while leaving
strobes active.
*Note: The AL1002ULADAJ will only synchronize horns, horn/strobes and strobes that contain synchronization capability
Contact signal manufacturer for more detailed info. The same synchronization mode must be selected for all outputs.
(AL800LGK Board)
Output Dip Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC