A.1 Four (4) Wire Smoke Detectors (cont.)
Smoke Detector/Base
Detector Type
Max Stand-by
Current (mA)
Alarm
Current (mA)
System Sensor 4WTR-B (12/24 volt)
I
3
Photo w/Therm/
Sounder/Relay
0.05
50
System Sensor 4WITAR-B (12/24 volt) I
3
Photo w/Isolated Therm/Sounder/Relay
0.05
50
System Sensor 2W-MOD2
I
3
Loop Test/Maintenance Mod.
0.05
*
System Sensor RRS-MOD
I
3
Reversing Relay/Sync Module
0.05
*
System Sensor 6424
Projected Beam
10
28.4
System Sensor Beam 1224(S)
Projected Beam
17
38.5
* Contact manufacturer for current draws
A.2 Door Holders
Table A-2 below lists door holders compatible with AL1002ULADAJ AUX output.
Manufacturer
Model
Type
Current (mA)
Edwards
DH150A
Floor Mount
96
Edwards
DH154A
Floor Mount
96
Edwards
DH158A
Surface Mount
96
Rixon Firemark
FM-980
Floor Mount, single
68
Rixon Firemark
FM-996
Surface Wiring
68
Rixon Firemark
FM-998
Concealed Wiring
68
A.3 Relays
Table A-3 below lists relays compatible with AL1002ULADAJ AUX output.
Manufacturer
Model
Current (mA)
Manufacturer
Model
Current (mA)
Air Products &
Controls, LTD
MR-101/C
MR-201/C
PAM-1
PAM-2
PAM-SD
A77-716B
15
35
15
15
15
20
System Sensor
PR-1
PR-2
PR-3
EOLR-1
R-10T
R-14T
R-20T
R-24T
R-10E
R-14E
R-20E
R-24E
15
30
30
30
23
23
40
40
23
23
40
40