Altronix NetWay1 Installation Instructions User Manual

Altronix Accessories for electrical

background image

NetWay1

- 1 -

Overview:

Altronix NetWay1 is a single port midspan PoE compliant power injector which provides power and passes data (e.g.
video) for PoE compliant devices. Devices may be located up to 100m (328 ft.) from NetWay1. A NetWayXT repeater
module can be utilized to extend the distance an additional 100m (328 ft.) for a total range of up to 200m (656 ft.).
A maximum range of 600m (1968 ft.) is possible using multiple repeaters, based on device port requirement. NetWay1 is
capable of supporting non-PoE compliant fixed IP cameras by utilizing NetWay1512 adapter.

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and
authorities having jurisdiction. Wiring should be UL Listed and/or Recognized wire suitable for the application.
Unit is intended to be used with a UL Listed Class 2 or LPS (limited power supply). NetWay1 is not intended to be
connected to outside plant leads and should be installed indoors within the protected premises.
NetWay1 is intended for indoor use only.

1. Mount NetWay1 in desired location utilizing the mounting hole (Fig. 1a, pg. 2). Use a proper fastener and/or wall

anchor when securing NetWay1 with screw through its mounting hole to the wall.

2. Connect 24VAC/24VDC to terminals marked [24VAC/VDC Input], (Fig. 1b, pg. 2). Use 22AWG-16AWG

wire for this connection. Input power should be a UL Listed Access Control power limited power supply (for UL294

applications) or Class 2 rated transformer/power supply (for UL60950-1 applications).

3. Connect structured cable from port marked [IN] on NetWay1 to the corresponding input of an UL Listed ethernet

switch or video server (Fig. 1b, pg. 2).

4. Connect structured cable from port marked [OUT] on the NetWay1 to PoE device (Fig. 1b, pg. 2).

All interconnected devices must be UL Listed.

5. Port status LED will illuminate indicating normal operation (Fig. 1c, pg. 2).

6. To initiate PoE shutdown connect 12VAC to 24VAC or 5VDC to 24VDC to the input terminals marked [PoE Shutdown]

on the NetWay1 (Fig. 1b, pg. 2). The PoE output voltage may be shutdown by manually applying voltage in the rated

range

(PoE Shutdown Voltage Range in Specifications). Upon applying voltage the output will drop to zero volts.

Removal of voltage from the shutdown terminals or applying zero volts to the shutdown terminals will allow the PoE

output to operate normally to supply power to PoE compliant devices.

Note: Return to normal operation from shutdown can take about 4 seconds. Although there is no output voltage to

power PoE devices during shutdown, data signals may still be present on the data pair lines of the CAT5 cable.

Agency Listings:

• UL/CUL Listed for Information

Technology Equipment (UL 60950-1).

• UL Listed for Access Control Systems (UL294).
Power over Ethernet (PoE) for Access Control
(UL294B).

CUL Listed - CSA Standard C22.2 No.205-M1983,

Signal Equipment.

• CE approved.

Input:

• 24VAC @ 1.2 amp or 24VDC @ 1.2 amp.

Data:

• One (1) PoE port provides power and passes data
over ethernet (CAT5) cable up to 100m (328 ft.).
• Data rate: 10/100 BASE-T compliant.

Output Power:

• Port provides up to 15.4W max.

• IEEE 802.3af compliant.

Output Power (cont’d):

• 48VDC.

• Short circuit protection.

Functions:

• Port status LED.

• PoE manual shutdown (For UL 60950-1 applications

only) (see Technical Specifications table pg. 4).

• Auto detection and protection of legacy

non-PoE cameras/devices.

• Compact insulated housing.

• Spring terminals (input and PoE shutdown).

Accessories:

NetWay1512:

• 13W adapter for non-PoE compliant IP cameras.

(For UL 60950-1 applications only).

NetWayXT:

• PoE repeater module extends range 100m (328 ft.).

(For UL 60950-1 applications only).

Features:

Installation Guide

NetWay1 - Single Port PoE Injector

for Standard Network Infrastructure

®

Rev. 102609