Altronix Tempo2 Installation Instructions User Manual
Tempo2 - one-shot/test timer

Overview:
Model Tempo2 Digital Test / Trigger Mode Timer is suitable for many applications that require a timed operation. e.g.
delayed egress with a programmable 1-60 second door release after delay expires, door prop alarm, door annunciator,
alarm swinger eliminator, etc. Digital display facilitates ease of programming and indicates time remaining before relay
activation. Daily/Weekly test mode can be used to trigger digital communicators or radio transmitters and provide Central
Stations with an alarm test signal.
Specifications:
• Input 12 or 24 Volts AC or DC operation.
• Triggers via dry contact closure.
• Output dry Form “C” contacts are 2 amp @ 120VAC/28VDC.
• LCD display facilitates programming and indicates countdown status.
• Current draw: stand-by 15mA, relay energized 30mA.
• Dual function: test timer/one shot.
• EE Prom memory protects against loss of programming due to power failure.
• Board dimensions (L x W x H approximate): 3” x 2.5” x 0.75” (76.2mm x 63.5mm x 19.05mm)
One-Shot Features (trigger activated):
• Programmable relay activation at the start or end of the timing cycle.
a. Delayed Pulse Mode:
- 1 to 60 sec. programmable pulse at the end of timing cycle.
b. Delay Mode:
- Relay can be programmed to energize or de-energize during
timing cycle (Digitally adjust from 1 sec.-24hours).
Test Timer Options:
• Programmable weekly or daily test. (Test can be programmed for
a specific day and time).
1. Depress and Hold Confirm
SU 00:00
will appear in display.
for 2 seconds until
TestMode
2. Depress Advance
SU 00:00
will appear in display.
SetClock
3. Depress and Hold Confirm
SU 00:00
will appear in display.
for two (2) seconds
Set day
Enter the current day of the week by depressing Advance
to make the selection.
4. Depress Confirm
SU 00:00
will appear in display.
Set hour
Enter the current hour of day by depressing Advance to make the selection.
5. Depress Confirm
SU 00:00
will appear in display.
Set min
Enter the current minute of day by depressing Advance to make the selection.
6. Depress Confirm
SU 00:00
will appear in display.
TestMode
Tempo2 - One-Shot/Test Timer
Dry
relay
output
Advance
C
NC
NO
POWER
12-24
VDC/VAC
Dry
Trigger
IN1
Confirm