beautypg.com

Altronix SMP7PMP8CB Installation Instructions User Manual

Smp7ctx series - installation guide

background image

Power Supply Voltage Output Specifications: *

Output VDC

Switch Position

Max. Load DC

12VDC

SW1 - Closed (Fig. 1B, pg. 3)

6 amp

24VDC

SW1 - Open (Fig. 1B, pg. 3)

6 amp

*Specified at 25˚ C ambient.

Installation Instructions:

The unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the unit in desired location.
2. Set SW1 on the power supply board to the desired DC output voltage

(Power Supply Voltage Output Specification Chart).

3. Connect AC power to terminals marked [L & N], connect ground to terminal marked [G] (if used).
4. Measure output voltage before connecting devices. This helps avoid potential damage.
5. Connect devices to be powered:

a. For Power Supply Board connect to terminals marked [+ DC --].
b. For Power Distribution Module(s) connect devices to be powered to terminal pairs 1 to 4 marked

SMP7CTX

-

1

-

-

-

-

1.45

6

SMP7PMCTX

-

1

-

-

-

x

1.45

6

SMP7PMP4

PD4

4

x

-

3.5

x

1.45

6

SMP7PMP4CB

PD4CB

4

-

x

2.5

x

1.45

6

SMP7PMP8

PD8

8

x

-

3.5

x

1.45

6

SMP7PMP8CB

PD8CB

8

-

x

2.5

x

1.45

6

SMP7PMP16

PD16W

16

x

-

3.5

x

1.45

6

SMP7PMP16CB

PD16WCB 16

-

x

2.5

x

1.45

6

Altronix

Model Number

Accessor

y P

ow

er

Distrib

ution

Module(s)Number of Outputs

Fused Outputs

PTC Outputs

Indi

vidual

Output Rating (amp)

115V

A

C / 60Hz

Input Cur

rent (amp)

12/24VDC

Total

Output Cur

rent (amp)

SMP7CTX Series Power Supply Configuration Reference Chart:

Overview:

These units will convert a 115VAC / 60Hz input, into a regulated 12VDC or 24VDC output up to 6 amp of
continuous load current (see specifications).

Specifications:

• Maximum charge current .7 amp.
• Filtered and electronically regulated outputs.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when

AC fails (zero voltage drop).

• AC input and DC output LED indicators.
• Short circuit and thermal overload protection.

• Complete with power supply, power distribution module

(when applicable), enclosure, cam lock & battery leads.

• Power on-off switch.
Supervised models only:

• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).

- 1 -

SMP7CTX Series - Installation Guide

Super

vised