Power Supply Voltage Output Specifications: *
Output VDC
Switch Position
Max. Load DC
12VDC
SW1 - Closed (Fig. 1B, pg. 3)
6 amp
24VDC
SW1 - Open (Fig. 1B, pg. 3)
6 amp
*Specified at 25˚ C ambient.
Installation Instructions:
The unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the unit in desired location.
2. Set SW1 on the power supply board to the desired DC output voltage
(Power Supply Voltage Output Specification Chart).
3. Connect AC power to terminals marked [L & N], connect ground to terminal marked [G] (if used).
4. Measure output voltage before connecting devices. This helps avoid potential damage.
5. Connect devices to be powered:
a. For Power Supply Board connect to terminals marked [+ DC --].
b. For Power Distribution Module(s) connect devices to be powered to terminal pairs 1 to 4 marked
SMP7CTX
-
1
-
-
-
-
1.45
6
SMP7PMCTX
-
1
-
-
-
x
1.45
6
SMP7PMP4
PD4
4
x
-
3.5
x
1.45
6
SMP7PMP4CB
PD4CB
4
-
x
2.5
x
1.45
6
SMP7PMP8
PD8
8
x
-
3.5
x
1.45
6
SMP7PMP8CB
PD8CB
8
-
x
2.5
x
1.45
6
SMP7PMP16
PD16W
16
x
-
3.5
x
1.45
6
SMP7PMP16CB
PD16WCB 16
-
x
2.5
x
1.45
6
Altronix
Model Number
Accessor
y P
ow
er
Distrib
ution
Module(s)Number of Outputs
Fused Outputs
PTC Outputs
Indi
vidual
Output Rating (amp)
115V
A
C / 60Hz
Input Cur
rent (amp)
12/24VDC
Total
Output Cur
rent (amp)
SMP7CTX Series Power Supply Configuration Reference Chart:
Overview:
These units will convert a 115VAC / 60Hz input, into a regulated 12VDC or 24VDC output up to 6 amp of
continuous load current (see specifications).
Specifications:
• Maximum charge current .7 amp.
• Filtered and electronically regulated outputs.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when
AC fails (zero voltage drop).
• AC input and DC output LED indicators.
• Short circuit and thermal overload protection.
• Complete with power supply, power distribution module
(when applicable), enclosure, cam lock & battery leads.
• Power on-off switch.
Supervised models only:
• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).
- 1 -
SMP7CTX Series - Installation Guide
Super
vised