Power Supply/Chargers Operating Guide
Models Include:
Model
Input
120VAC, 60Hz
Output
Power-
Limited
Auxiliary Power-Limited
Output (unswitched)
Ripple
Voltage
12VDC
24VDC
eFlow4N,
eFlow4N8,
eFlow4N8D
3.5 amp
4 amp
4 amp
3
1 amp
730mV
eFlow4NX,
eFlow4NX8,
eFlow4NX8D
Overview:
The eFlow4N series power supply/chargers convert a 120VAC, 60Hz input, to a 12VDC or 24VDC output.
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH
0.4 amp/4 amp
N/A
15 Mins./4 amp
12AH
1 amp/4 amp
0.3 amp/4 amp
35 Mins./4 amp
40AH
4 amp/4 amp
1.2 amp/4 amp
Over 4 Hours/4 amp
65AH
4 amp/4 amp
1.5 amp/4 amp
Over 4 Hours/4 amp
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54 amp.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous
with no interruption.
LED Diagnostics:
Red (DC)
Green (AC/AC1) Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Installing Company: _________________________________ Service Rep. Name: ___________________________________________________
Address: _______________________________________________________________________ Phone #: _______________________________
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow4N Series, Rev. 4NRP052213 for complete
instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 4NRP052213