Power Supply/Chargers Operating Guide

Models Include:

Model

Input

120VAC, 60Hz

Output

Power-

Limited

Auxiliary Power-Limited

Output (unswitched)

Ripple

Voltage

12VDC

24VDC

eFlow4N,
eFlow4N8,
eFlow4N8D

3.5 amp

4 amp

4 amp

3

1 amp

730mV

eFlow4NX,
eFlow4NX8,
eFlow4NX8D

Overview:

The eFlow4N series power supply/chargers convert a 120VAC, 60Hz input, to a 12VDC or 24VDC output.

Stand-by Specifications:

Battery

Burg. Applications

4 hr. Stand-by/

15 min. Alarm

Fire Applications

24 hr. Stand-by/

5 min. Alarm

Access Control

Applications

Stand-by

7AH

0.4 amp/4 amp

N/A

15 Mins./4 amp

12AH

1 amp/4 amp

0.3 amp/4 amp

35 Mins./4 amp

40AH

4 amp/4 amp

1.2 amp/4 amp

Over 4 Hours/4 amp

65AH

4 amp/4 amp

1.5 amp/4 amp

Over 4 Hours/4 amp

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54 amp.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous
with no interruption.

LED Diagnostics:

Red (DC)

Green (AC/AC1) Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Installing Company: _________________________________ Service Rep. Name: ___________________________________________________

Address: _______________________________________________________________________ Phone #: _______________________________

Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow4N Series, Rev. 4NRP052213 for complete
instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 4NRP052213