6 Set up with the display and adjustment module
VEGAFLEX 82 • Profibus PA
44220-EN-130910
You can find "Extended adjustment" in the next sub-chapter.
Sensor address
In the first menu item you have to enter a sensor address. The selec-
tion switches on the electronics module are preset to sensor address
126. This means that the sensor address can be changed via the
display and adjustment module.
If you set a sensor address with the selection switches which is lower
than 126, the set value is applicable. In such case, the address setting
via the display and adjustment module has no effect.
Measurement loop name
In the next menu item you can assign a suitable measurement loop
name. You can enter a name with max. 19 characters.
Application
In this menu item, you can select the application. You can choose
between level measurement and interface measurement. You can
also choose between measurement in a vessel or in a bypass or
standpipe.
Medium - dielectric constant
In this menu item, you can define the type of medium (product).
Max. adjustment
In this menu item, you can enter the max. adjustment for the level.
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. The distance refers to the sensor
reference plane (seal surface of the process fitting). Keep in mind that
the max. level must lie below the dead band.
Min. adjustment
In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.
distance from the flange to the probe end) corresponding to the per-
centage value. The distance refers tot he sensor reference plane (seal
surface of the process fitting).
General information
Level measurement