32

6 Set up with the display and adjustment module

VEGAFLEX 82 • Profibus PA

44220-EN-130910

You can find "Extended adjustment" in the next sub-chapter.
Sensor address

In the first menu item you have to enter a sensor address. The selec-

tion switches on the electronics module are preset to sensor address

126. This means that the sensor address can be changed via the

display and adjustment module.

If you set a sensor address with the selection switches which is lower

than 126, the set value is applicable. In such case, the address setting

via the display and adjustment module has no effect.
Measurement loop name

In the next menu item you can assign a suitable measurement loop

name. You can enter a name with max. 19 characters.
Application

In this menu item, you can select the application. You can choose

between level measurement and interface measurement. You can

also choose between measurement in a vessel or in a bypass or

standpipe.

Medium - dielectric constant

In this menu item, you can define the type of medium (product).
Max. adjustment

In this menu item, you can enter the max. adjustment for the level.
Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.
Min. adjustment

In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

General information

Level measurement