11 Supplement

VEGAPULS 67 • Modbus and Levelmaster protocol

41369-EN-121011

11.6 Thermo Electron Autopilot

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

2

3

13

45

2o

ff

on

( )

(

)

(-)

(-)

+8

+30 Vdc

to

GND

2

1

Rx -

Rx+

Fig. 54: Connection of VEGAPULS 67 to RTU Thermo Electron Autopilot
1 VEGAPULS 67

2 RTU Thermo Electron Autopilot

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

IEE Fit 2R

Input Register Base Number

0

The basic number of the input registers is always added to the input register address of VEGAPULS

67.
Address 1300 must hence be entered as register address for 1300 for RTU Thermo Electron Auto-

pilot.