background image

19

4 Mounting

VEGAPULS 67 • Modbus and Levelmaster protocol

41369-EN-121011

If the medium has good reflective properties, VEGAPULS 67 can

also be mounted on a longer socket piece. Recommended values

for socket heights are specified in the following illustration. You must

carry out a false echo storage afterwards.

d

h

The below charts specify the max. socket piece length h depending

on the diameter d.

Socket diameter d

Socket length h

80 mm

300 mm

100 mm

400 mm

150 mm

500 mm

Socket diameter d

Socket length h

3"

11.8 in

4"

15.8 in

6"

19.7 in

Tip:

In new facilities it is useful to incline the vessel socket in the direction

of the outlet. False reflections from the vessel wall are thus reduced

and measurement all the way down to the bottom of the conical outlet

is possible.