4 measurement error with constant level – VEGA VEGAPULS 67 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 54
54
9 Diagnosis, Asset Management and service
VEGAPULS 67 • Modbus and Levelmaster protocol
41369-EN-121011
•
Evaluation of fault messages, for example via the indicating and
adjustment module
•
Checking the output signal with 4 … 20 mA instruments
•
Treatment of measurement errors
Further comprehensive diagnostics options offer a PC with the soft-
ware PACTware and the suitable DTM. In many cases, the reasons
can be determined in this way and faults can be rectified.
The below tables show typical examples for application-relevant
measurement errors with bulk solids. There are two measurement
errors:
•
Constant level
•
Filling
•
Emptying
The images in column "Error pattern" show the real level with a bro-
ken line and the level displayed by the sensor as a continuous line.
1
2
Level
time
0
1 Real level
2 Level displayed by the sensor
Instructions:
•
Wherever the sensor displays a constant value, the reason could
also be the fault setting of the current output to "Hold value"
•
In case of a too low level indication, the reason could be a line
resistance that is too high
9.4 Measurement error with constant level
Fault description
Error pattern
Cause
Rectification
1. Measured value
shows a too low or too
high level
Level
time
0
– Min./max. adjustment not
correct
– Adapt min./max. adjustment
– Wrong linearization curve
– Adapt linearization curve
2. Measured value
jumps towards 100 %
Level
time
0
– Due to the process, the ampli-
tude of the product echo sinks
– A false signal suppression was
not carried out
– Carry out false signal suppres-
sion
– Amplitude or position of a
false echo has changed (e.g.
condensation, buildup); false
signal suppression no longer
matches
– Determine the reason for the
changed false echo, carry out
false signal suppression, e.g.
with condensation
Treatment of measure-
ment errors with bulk
solids