5 levelmaster commands, 5 parameters for the bus communication – VEGA VEGAPULS 67 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 70
70
11 Supplement
VEGAPULS 67 • Modbus and Levelmaster protocol
41369-EN-121011
Parameter
Length
Code/Data
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Object ID
1 Byte
0x00 to 0xFF
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x2B
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Confirmity Level
1 Byte
0x01, 0x02, 0x03, 0x81, 0x82, 0x83
More follows
1 Byte
00/FF
Next Object ID
1 Byte
Object ID number
Number of Objects
1 Byte
List of Object ID
1 Byte
List of Object length
1 Byte
List of Object value
1 Byte
Depending on the Object ID
11.5 Levelmaster commands
The VEGAPULS 67 is also suitable for connection to the following RTUs with Levelmaster protocol.
The Levelmaster protocol is often called "Siemens" "Tank protocol".
RTU
Protocol
ABB Totalflow
Levelmaster
Kimray DACC 2000/3000
Levelmaster
Thermo Electron Autopilot
Levelmaster
11.5 Parameters for the bus communication
The VEGAPULS 67 is preset with the default values:
Parameter
Configurable Values
Default Value
Baud Rate
1200, 2400, 4800, 9600, 19200
9600
Start Bits
1
1
Data Bits
7, 8
8
Parity
None, Odd, Even
None
Stop Bits
1, 2
1
Address range Levelmaster
32
32
The Levelmaster commands are based on the following syntax:
•
Capital letters are at the beginning of certain data fields
•
Small letters stand for data fields
•
All commands are terminated with "
•
All commands start with "Uuu", whereby "uu" stands for the address (00-31)