6 exchanging the electronics module – VEGA VEGABAR 86 HART and accumulator pack - Operating Instructions User Manual
Page 44
44
8 Diagnosis, asset management and service
VEGABAR 86 • HART and accumulator pack
45040-EN-131107
•
F
T
: Thermal change of zero signal and output span
•
F
Kl
: Deviation
•
F
a
: Thermal change of the current output
You can find the specifications in chapter "Technical data".
Level measurement 1500 mmWs
Product temperature up to 40 °C
VEGABAR 86 with measuring range 0.2 bar
Deviation < 0.1 %
Calculation ΔT: ΔT = 40 °C - 20 °C = 20 K
Calculation of the set Turn Down:
TD = 200 mbar/147 mbar, TD = 1.4
1. step: Calculation of the basic accuracy
F
perf
= √((F
T
)
2
+ (F
Kl
)
2
)
F
T
= (0.15 %) x (0.5 + 0.5 x TD)
F
Kl
= 0.1 %
F
perf
= √((0.15 %) x (0.5 + 0.5 x TD)
2
+ (0.1 %)
2
)
F
perf
= 0.21 %
Step 2: Calculation of the total deviation
F
total
= F
perf
+ F
stab
F
stab
= (0.05 % x TD)
F
stab
= (0.05 % x 1.4)
F
stab
= 0.07 %
F
total
= 0.21 % + 0.07 % = 0.28 %
1. step: Calculation of the basic accuracy
F
perf
= √((F
T
)
2
+ (F
Kl
)
2
+ (F
a
)
2
)
F
T
= (0.15 %) x (0.5 + 0.5 x TD)
F
Kl
= 0.1 %
F
a
= 0.15 %
F
perf
= √((0.15 %) x (0.5 + 0.5 x TD)
2
+ (0.1 %)
2
+ (0.15 %)
2
)
F
perf
= 0.25 %
Step 2: Calculation of the total deviation
F
total
= F
perf
+ F
stab
F
stab
= (0.05 % x TD)
F
stab
= (0.05 % x 1.4)
F
stab
= 0.07 %
F
total
= 0.25 % + 0.07 % = 0.32 %
8.6 Exchanging the electronics module
In case of a defect, the user can replace the electronics module with
another one of identical type.
Practical example
Calculation - Digital out-
put signal
Calculation - Analogue
output signal