VEGA VEGABAR 86 HART and accumulator pack - Operating Instructions User Manual

Page 32

background image

32

6 Set up with the display and adjustment module

VEGABAR 86 • HART and accumulator pack

45040-EN-131107

Menu item

Parameter

Default value

Current output

Current output -

Mode

Output characteristics
4 … 20 mA
Reaction when malfunction occurs
≤ 3.6 mA

Current output -

Min./Max.

3.8 mA
20.5 mA

Lock adjustment

Released

Reset - Display

Menu item

Default value

Menu language

Order-specific

Displayed value 1

Current output in %

Displayed value 2

Measuring cell temperature in °C

Backlight

Switched off

Reset - Diagnosis

Menu item

Parameter

Default value

Sensor status

-

Peak value

Pressure

Actual measured value

Temperature

Actual temperature values from meas-

uring cell, electronics

Simulation

Process pressure

Reset - Additional settings

Menu item

Parameter

Default value

PIN

0000

Date/Time

Actual date/Actual time

Copy in-

strument

settings
Special pa-

rameters

No reset

Scaling

Scaling size

Volume in l

Scaling format

0 % corresponds to 0 l
100 % corresponds to 0 l

Current out-

put

Current output - Size

Lin. percent - Level

Current output - adjustment

0 … 100 % correspond to

4 … 20 mA

HART mode

Address 0

The instrument settings are copied with this function. The following

functions are available:

Additional adjustments -

Copy instrument settings