beautypg.com

VEGA VEGABAR 86 HART and accumulator pack - Operating Instructions User Manual

Page 27

background image

27

6 Set up with the display and adjustment module

VEGABAR 86 • HART and accumulator pack

45040-EN-131107

5. Save settings with [OK] and move with [ESC] and [->] to the max.

adjustment.

The min. adjustment is finished.
For an adjustment with filling, simply enter the actual measured value

indicated at the bottom of the display.

Proceed as follows:
1. Select with [->] the menu item "Max. adjustment" and confirm

with [OK].

2. Edit the percentage value with [OK] and set the cursor to the

requested position with [->].

3. Set the requested percentage value (e.g. 90 %) with [+] and save

with [OK]. The cursor jumps now to the pressure value.

4. Enter the pressure value for the full vessel (e.g. 900 mbar) cor-

responding to the percentage value.

5. Save settings with [OK]
The max. adjustment is finished.
For an adjustment with filling, simply enter the actual measured value

indicated at the bottom of the display.

To damp process-dependent measured value fluctuations, set an

integration time of 0 … 999 s in this menu item. The increment is 0.1 s.

Depending on the sensor type, the factory setting is 0.1 s.

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. a horizontal cylindri-

cal or spherical tank - and the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed for

these vessels. They represent the correlation between the level per-

centage and vessel volume. The linearization applies to the measured

value indication and the current output.

Caution:

Note the following, if the respective sensor is used as part of an over-

fill protection system according to WHG:
If a linearization curve is selected, the measuring signal is no longer

necessarily linear to the filling height. This must be considered by the

Setup - Max. adjustment

Level

Setup - Damping

Setup - Linearization