11 Supplement

VEGADIF 65 • Foundation Fieldbus

36130-EN-130417

Ʋ acyclically approx.

50 ms

Damping (63 % of the input variable)

0 … 999 s, adjustable

Additional output parameter - temperature
Processing is made via output signal HART multidrop, Profibus PA and Foundation Fieldbus
Range

-50 … +150 °C (-58 … +302 °F)

Resolution

1 °C (1.8 °F)

Accuracy in the range of 0 … +100 °C

(+32 … +212 °F)

±3 K

Accuracy in the range of -50 … 0 °C

(-58 … +32 °F) and +100 … +150 °C

(+212 … +302 °F)

typ. ±3 K

Input variable
Measured variable

Differential pressure, flow and level derived from it

Adjustment differential pressure
Adjustment range of the zero/span adjustment relating to the nominal measuring range:

Ʋ Pressure value zero

-120 … +120 %

Ʋ Pressure value span

zero + (-220 … +220 %)

9)

Adjustment level
Adjustment range of the min./max. adjustment relating to the nominal measuring range:

Ʋ Percentage value

-10 … +110 %

Ʋ Pressure value

-120 … +120 %

10)

Adjustment flow
Adjustment range of the zero/span adjustment relating to the nominal measuring range:

Ʋ Pressure value zero

-120 … +120 %

Ʋ Pressure value span

-120 … +120 %

11)

Recommended max. turn down

15 : 1 (no limitation)

Nominal measuring ranges, measurement limits and smallest spans to be calibrated

Nominal range

Lower measurement

limit

Upper measuring limit

Smallest adjustable

span

10 mbar (1 kPa)

-10 mbar (-1 kPa)

+10 mbar (+1 kPa)

0.25 mbar (25 Pa)

30 mbar (3 kPa)

-30 mbar (-3 kPa)

+30 mbar (+3 kPa)

0.3 mbar (30 Pa)

100 mbar (10 kPa)

-100 mbar (-10 kPa)

+100 mbar (+10 kPa)

1 mbar (100 Pa)

500 mbar (50 kPa)

-500 mbar (-50 kPa)

+500 mbar (+50 kPa)

5 mbar (500 Pa)

3 bar (300 kPa)

-3 bar (-300 kPa)

+3 bar (+300 kPa)

30 mbar (3 kPa)

16 bar (1600 kPa)

-16 bar (-1600 kPa)

+16 bar (+1600 kPa)

160 mbar (16 kPa)

40 bar (4000 kPa)

-40 bar (-4000 kPa)

+40 bar (+4000 kPa)

400 mbar (40 kPa)

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

9)

Values less than -1 bar cannot be set.

10)

Values less than -1 bar cannot be set.

11)

Values less than -1 bar cannot be set.