beautypg.com

8 setup, 1 select the mode, 2 flow measurement – VEGA VEGADIF 65 Foundation Fieldbus User Manual

Page 57

background image

57

8 Setup

VEGADIF 65 • Foundation Fieldbus

36130-EN-130417

8 Setup

8.1 Select the mode

The following operating modes can be set on VEGADIF 65:

Flow measurement

Level measurement

Differential pressure measurement

8.2 Flow measurement

In flow measurement, VEGADIF 65 is normally used without a chemi-

cal seal.
Before adjusting VEGADIF 65, you have to clean the effective pres-

sure lines and the instrument must be filled with the medium.

+

I

II

+

6

7

3

2

4

A

B

Fig. 50: Preferred measurment setup for gases
I VEGADIF 65

II 3-fold valve block

2.4 Inlet valves

3 Breather valve

6.7 Vent valves on VEGADIF 65

A, B Blocking valves

Instructions

Measurement setup for

gases