4 Mounting

VEGADIF 65 • Foundation Fieldbus

36130-EN-130417

Detailed instructions for mounting the DP flow element are stated in

DIN EN ISO 5167 as well as in the instrument documentation from the

respective manufacturer.

You will find general recommendations for the installation of effective

pressure lines in the corresponding national or international stand-

ards. When installing effective pressure lines outdoors, consider

applying suitable anti-freeze protection, e.g. tube heating. Install

effective pressure lines with a monotonic downward slope of at least

10 %.

In case of strong vibrations at the application position, the instrument

version with external electronics should be used.

Higher process temperatures often mean also higher ambient tem-

peratures for electronics and connection cable. Make sure that the

upper temperature limits stated in chapter "Technical data" for the

environment of the electronics housing and connection cable are not

exceeded.

4.2 Instructions for oxygen applications

Oxygen and other gases can be explosive when brought into contact

with oils, grease and plastics, so the following measures must also be

taken:

All components of the plant, such as e.g. measuring instru-

ments must be cleaned according to the requirements of BAM

(DIN 19247)

Depending on the seal material, certain temperatures and pres-

sures must not be exceeded in oxygen applications, see chapter

"Technical data"

Danger:

Instruments for oxygen applications must be unpacked just before

mounting. After removing the protective cover of the process fitting,

the label "O

2

" will be visible on the process fitting. Penetration of oil,

grease and dirt should be avoided. Danger of explosion!

4.3 Mounting and connection instructions

When connecting the VEGADIF 65 to the measurement loop, take

note of the plus/minus side of the process component. The plus side

is marked with a "+", the minus side with a "-" on the process compo-

nent next to the oval flanges.

Effective pressure lines

Vibrations

Temperature limits

Oxygen applications

Connection plus/minus

side