beautypg.com

VEGA Capacitive electrodes EK Profibus PA User Manual

Page 33

background image

Capacitive electrodes EK - Profibus PA

33

Setup

Key

Display

Adjust-
ment

Para-
meter
adjustment

Sensor

m(d)

4.700

OK

OK

with
medium

Min.
adjust
at %

-------

(Min. adjustment)

OK

OK

3. Conditioning

Under the menu item "Conditioning" you can
scale the display, set an integration time and
choose a linearisation curve.

Scaling

Here, you can scale the digital display of the
electrode.

0 % correspond

Here, you enter the value which should be
displayed when 0 % level is reached,
e.g. 20 l.

100 % correspond

Here, you enter the value which should be
displayed when 100 % level is reached, e.g.
1200 l.

If you want the value to be displayed and you
need for the max. value a number with more
than 4 digits, please choose the next higher
unit e.g. 14000 litres = 140 hl.

Decimal point

If necessary, set the position of the decimal
point. Keep in mind that max. 4 digits can be
displayed.

Unit

In the menu "Unit", you choose the physical
unit (%, t, ft

3

, in

3

, gal, in, lb, pF, m, cm, mm, ft,

yd, m

3

, kg, l, hl).

Linearisation curve

In the menu "Lin. curve" you can choose
between three standard linearisation curves.
Preadjusted is a linear dependency between
percentage value of the level and the
percentage value of filling volume.

You can choose between linear, cylindrical
tank, spherical tank and user-programmable
linearisation curve. Programming your own
linearisation curve is only possible with the
PC and the adjustment program VVO. A
user-programmable curve, however, can be
transferred from the PC to the electronics of
the instrument and called up under this menu
item.

Integration time

In the menu item "

Integration time", you can

set a delay (in seconds) for the signal output.

4. Outputs

Under the menu "

Outputs", you can

determine which parameter should be
outputted by the sensor display and the PA
output.