beautypg.com

Material cone, Mounting – VEGA Capacitive electrodes EK Profibus PA User Manual

Page 19

background image

Capacitive electrodes EK - Profibus PA

19

d

d

d

6

d

6

Mounting

Filling

Emptying

Material cone, filling and emptying centered

d

3

1

2

d

10

Filling

Emptying

1 Emptying
2 Filling opening
3 Capacitive

electrode

Material cone, filling centered, emptying laterally

Material cone

When installing the meas. probe in a vessel,
be aware that conical heaps which alter the
switching point can form in solid materials.
We recommend selecting an installation
location where the electrode detects the
average value of the conical heap.

The meas. probe must be installed in a way
that takes the filling and emptying apertures
of the vessel into account. To compensate
meas. errors caused by the conical heap,
you should install the electrode at a distance
of approx.

d

/

6

from the vessel wall.