Capacitive electrodes EK - Profibus PA

27

Electrical connection

Wiring example for the installation of an Ex system on vessels with cathodic
corrosion protection.

The following overvoltage arrester can be used:
----- B62-30 W:

B62-30 W:

B62-30 W:

B62-30 W:

B62-30 W: 9 … 36 V DC, max. 1 A

B

A

2
1

E2
E1

A2
A1

B62-30 W

E2
E1

A2
A1

B62-30 W

Ex area, zone 1 or zone 2

oscillator

transmitter

external earth
terminal

sensor

shielding

overvoltage arrester
in metal or plastic
housing

shielding

Non Ex area

switch cabinet/control room

signal
conditioning
instrument
or safety
barrier

optionally: ovevoltae
arrester

vessel zone
0

cathodic tank protection
2 … 24 V (object voltage)

insulated cable min.
4 mm

2

Cu

A

A cable with either metal cover, shielding or metallic protection tube according to VDE must be used
between overvoltage arrester and transmitter (metal cover, shielding or protection tube must be
connected to earth).
Test voltage of the cable "A"

1500 V AC.

B

A cable according to VDE, if necessary with metal cover or shielding must be used between control room
and overvoltage arrester. The metal cover or shielding - if necessary - must only be connected on the
transmitter side of the overvoltage arrester. The cable must have an outer insulation.
Test voltage of the cable "B" ³ 500 V AC.